Division 7 Products to be used in smoke and heat control systemsF1

United Kingdom

Original text. Later amendments are not shown.

The standards cited in this section are under preparation and may be due to revision or upgrade.

Notes

The classification is completed by the suffix ‘ single ’ to indicate suitability for single compartment use only.

In addition, the symbols, ‘v e ’ and/or ‘h o ’ indicate the suitability for vertical and/or horizontal use.

‘S’ indicates a leakage rate of less than 5 m 3 /hr/m 2 (All ducts without an ‘S’ classification must have a leakage rate of less than 10 m 3 /hr/m 2 )

‘ 500 ’ , ‘ 1 000 ’ , ‘ 1 500 ’ indicate the suitability for use up to these values of pressure, measured at ambient.

Applies to Single compartment smoke control ducts
Standard(s) EN 13501-4; EN 1363-1, 2, 3; EN 1366-9 EN 12101-7
Classification: —
E 300 30 60 90 120
E 600 30 60 90 120
Notes

The classification is completed by the suffix ‘ multi ’ to indicate suitability for multi-compartment use.

In addition, the symbols ‘v e ’ and/or ‘h o ’ indicate the suitability for vertical and/or horizontal use.

‘S’ indicates a leakage rate of less than 5 m 3 /hr/m 2 (All ducts without an ‘S’ classification must have a leakage rate of less than 10 m 3 /hr/m 2 )

‘ 500 ’ , ‘ 1 000 ’ , ‘ 1 500 ’ indicate the suitability for use up to these values of pressure, measured at ambient.

Applies to Multi-compartment fire resistant smoke control ducts
Standard(s) EN 13501-4; EN 1363-1, 2, 3; EN 1366-8; EN 12101-7
Classification: —
EI 30 60 90 120
Notes

The classification is completed by the suffix ‘ single ’ to indicate suitability for single compartment use.

‘HOT 400/30’ (high operational temperature) indicates that the damper has the ability to be opened or closed during a period of 30 minutes under temperature conditions below 400 °C (to be used only with E 600 classification).

‘v ed ’, ‘v ew ’‘v edw ’ and/or ‘h od ’, ‘h ow ’‘h odw ’ indicate the suitability for vertical and/or horizontal use, together with mounting in a duct or in a wall or both respectively.

‘S’ indicates a leakage rate of less than 200 m 3 /hr/m 2 . All dampers without an ‘S’ classification must have a leakage rate of less than 360 m 3 /hr/m 2 . All damper less than 200 m 3 /hr/m 2 take this value, all dampers between 200 m 3 /hr/m 2 and 360 m 3 /hr/m 2 take the 360 m 3 /hr/m 2 value. Leakage rates are both at ambient and elevated temperatures.

‘ 500 ’ , ‘ 1 000 ’ , ‘ 1 500 ’ indicates the suitability for use up to at these values of under pressure, measured at ambient.

‘ AA ’ or ‘ MA ’ indicates automatic activation or manual intervention

‘ i→o ’ , ‘ i ←o ’ , ‘ i ↔o ’ , indicates the performance criteria are satisfied from inside to outside, outside to inside or both respectively.

‘C 300 ’, ‘C 10000 ’, ‘C mod ’ indicates the suitability of the damper for use in smoke control only systems combined smoke control and environmental systems, or modulating dampers used in combined smoke control and environmental systems respectively.

Applies to Single compartment smoke control dampers
Standard(s) EN 13501-4; EN 1363-1, 3; EN 1366- 9, 10; EN 12101-8
Classification: —
E 300 30 60 90 120
E 600 30 60 90 120
Notes

The classification is completed by the suffix ‘ multi ’ to indicate suitability for multi-compartment use.

‘ HOT 400/30 ’ (high operational temperature) indicates that the damper has the ability to be opened or closed during a period of 30 minutes under temperature conditions below 400 °C.

‘v ed ’, ‘v ew ’‘v edw ’ and/or ‘h od ’, ‘h ow ’‘h odw ’ indicate the suitability for vertical and/or horizontal use, together with mounting in a duct or in a wall or both respectively.

‘S’ indicates a leakage rate of less than 200 m 3 /hr/m 2 . All dampers without an ‘S’ classification must have a leakage rate of less than 360 m 3 /hr/m 2 . All damper less than 200 m 3 /hr/m 2 take this value, all dampers between 200 m 3 /hr/m 2 and 360 m 3 /hr/m 2 take the 360 m 3 /hr/m 2 value. Leakage rates are both at ambient and elevated temperatures.

‘ 500 ’ , ‘ 1 000 ’ , ‘ 1 500 ’ indicates the suitability for use up to these values of pressure, measured at ambient.

‘ AA ’ or ‘ MA ’ indicates automatic activation or manual intervention

‘ i→o ’ , ‘ i ←o ’ , ‘ i ↔o ’ , indicates that the performance criteria are satisfied from inside to outside, outside to inside or both, respectively.

‘C 300 ’, ‘C 10000 ’, ‘C mod ’ indicates the suitability of the damper for use in smoke control only systems, combined smoke control and environmental systems, or modulating dampers used in combined smoke control and environmental systems, respectively.

Applies to Multi-compartment fire resistant smoke control dampers
Standard(s) EN 13501-4; EN 1363-1, 2, 3; EN 1366-2, 8, 10; EN 12101-8
Classification:
EI 30 60 90 120
E 30 60 90 120
Notes

‘A’ can be any time over 120 minutes.

Applies to Smoke barriers
Standard(s) EN 13501-4; EN 1363-1, 2; EN 12101-1
Classification: D
D 600 30 60 90 120 A
DH 30 60 90 120 A

Notes

Applies to Powered smoke and heat exhaust ventilators (fans), connecting joints
Standard(s) EN13501-4; EN 1363-1; EN 12101-3; ISO 834-1
Classification: F
F 200 120
F 300 60
F 400 90 120
F 600 60
F 842 30
Notes

Where θ indicates the exposure condition (temperature).

Applies to Natural smoke and heat exhaust ventilators
Standard(s) EN 13501-4; EN 1363-1; EN 12101-2
Classification: B
B 300 30
B 600 30
B θ 30

Annotations

Textual amendments

F1

Inserted by Commission Decision of 27 August 2003 amending Decision 2000/367/EC establishing a classification system for resistance-to-fire performance for construction products, as regards the inclusion of smoke and heat control products (notified under document number C(2003) 2851) (Text with EEA relevance) (2003/629/EC).