The tables set out in this annex list construction products and/or materials which satisfy all the requirements for the performance characteristic reaction to fire without need for testing.

F1Table 1

Classes of reaction to fire performance for wood-based panels

Mounted without an air gap directly against class A1 or A2-s1, d0 products with minimum density 10 kg/m 3 or at least class D-s2, d2 products with minimum density 400 kg/m 3 .

A substrate of cellulose insulation material of at least class E may be included if mounted directly against the wood-based panel, but not for floorings.

Mounted with an air gap behind. The reverse face of the cavity shall be at least class A2-s1, d0 products with minimum density 10 kg/m 3 .

Mounted with an air gap behind. The reverse face of the cavity shall be at least class D-s2, d2 products with minimum density 400 kg/m 3 .

Veneered, phenol- and melamine-faced panels are included for class excl. floorings.

A vapour barrier with a thickness up to 0,4 mm and a mass up to 200 g/m 2 can be mounted in between the wood-based panel and a substrate if there are no air gaps in between.

Class as provided for in Table 1 of the Annex to Decision 2000/147/EC.

Class as provided for in Table 2 of the Annex to Decision 2000/147/EC.

Product EN product standard End use condition f1 Minimum density (kg/m 3 ) Minimum thickness (mm) Class f2 (excluding floorings) Class f3 (floorings)
Cement-bonded particleboard f4 EN 634-2 without an air gap behind the panel 1 000 10 B-s1, d0 B fl -s1
Fibreboard, hard EN 622-2 without an air gap behind the wood-based panel 900 6 D-s2, d0 D fl -s1
Fibreboard, hard f5 EN 622-2 with a closed air gap not more than 22 mm behind the wood-based panel 900 6 D-s2, d2 —
Particleboard , f6 , f7 EN 312 without an air gap behind the wood-based panel 600 9 D-s2, d0 D fl -s1
Fibreboard, hard and medium , ,

EN 622-2

EN 622-3

MDF , , EN 622-5
MDF , , EN 300
Plywood , , EN 636 -“- 400 9 D-s2, d0 D fl -s1
Solid wood panel , , EN 13353 12
Flaxboard , , EN 15197 -“- 450 15 D-s2, d0 D fl -s1
Particleboard , EN 312 with a closed or an open air gap not more than 22 mm behind the wood-based panel 600 9 D-s2, d2 —
Fibreboard, hard and medium ,

EN 622-2

EN 622-3

MDF , EN 622-5
OSB , EN 300
Plywood , EN 636 -“- 400 9 D-s2, d2 —
Solid wood panel , EN 13353 12
Particleboard f8 , EN 312 with a closed air gap behind the wood-based panel 600 15 D-s2, d0 D fl -s1
Fibreboard, medium , EN 622-3
MDF , EN 622-5
OSB , EN 300
Plywood , EN 636 -“- 400 15 D-s2, d1 D fl -s1
Solid wood panel , EN 13353 D-s2, d0
Flaxboard , EN 15197 -“- 450 15 D-s2, d0 D fl -s1
Particleboard , EN 312 with an open air gap behind the wood-based panel 600 18 D-s2, d0 D fl -s1
Fibreboard, medium , EN 622-3
MDF , EN 622-5
OSB , EN 300
Plywood , EN 636 -“- 400 18 D-s2, d0 D fl -s1
Solid wood panel , EN 13353
Flaxboard , EN 15197 -“- 450 18 D-s2, d0 D fl -s1
Particleboard EN 312 any 600 3 E E fl
OSB EN 300
MDF EN 622-5 -“- 400 3 E E fl
250 9 E E fl
Plywood EN 636 -“- 400 3 E E fl
Fibreboard, hard EN 622-2 -“- 900 3 E E fl
Fibreboard, medium EN 622-3 -“- 400 9 E E fl
Fibreboard, soft EN 622-4 -“- 250 9 E E fl

F2 F3Table 2

Classes of reaction — to — fire performance of gypsum plasterboards

Determined according to EN ISO 536 and with no more than 5 % organic additive content.

Classes as provided for in Table 1 of the Annex to Commission Decision 2000/147/EC.

Gypsum plasterboard Nominal board thickness (mm) Gypsum core Paper grammage f9 (g/m 2 ) Substrate Class f10 (excluding floorings)
Density (kg/m 3 ) Reaction to fire class
Conforming to EN 520 (except perforated boards) ≥ 6,5 < 9,5 ≥ 800 A1 ≤ 220 Any wood-based product with density ≥ 400 kg/m 3 or any product of at least class A2-s1, d0 A2-s1, d0
> 220 ≤ 320 B-s1, d0
≥ 9,5 ≥ 600 ≤ 220 Any wood-based product with density ≥ 400 kg/m 3 or any product of at least class A2-s1, d0 or any insulating product of at least class E-d2 mounted according to method 1 A2-s1, d0
> 220 ≤ 320 B-s1, d0

Table 3

Classes of reaction-to-fire performance of high-pressure decorative laminate panels

Either directly fixed (i.e. with no air gap) to a material having a reaction to fire of A2-s1, d0 or better and a density of at least 600 kg/m 3 , or mounted on a timber or metal batten support frame, with a non-ventilated (i.e. void open only at the top) air gap of at least 30 mm, the reverse face of the cavity so formed having a reaction to fire classification of A2-s1, d0 or better.

Classes as provided for in Table 1 of the Annex to Decision 2000/147/EC.

Complying with European Standard EN 438-7.

High pressure decorative laminate panels f11 Product detail Minimum density (kg/m 3 ) Minimum overall thickness (mm) Class f12 (excluding floorings)
Interior grade non-FR Compact HPL panels f13 Compact HPL meeting EN 438-4 type CGS 1 350 6 D-s2, d0
Interior grade non-FR HPL composite panels with wood-based substrates Composite panels comprising non-FR grade HPL meeting the requirements of EN 438-3, adhesively bonded to both sides of non-FR grade wood-based core of minimum thickness 12 mm complying with EN 13986, using PVAc or thermosetting adhesive at an application rate of 60 to 120 g/m 2

Wood-based core minimum density 600

HPL minimum density 1 350

12 mm wood-based core with HPL ≥ 0,5 mm bonded to both sides D-s2, d0

Table 4

Classes of reaction-to-fire performance of structural timber products f14

Applies to all species covered by the product standards.

Classes as provided for in Table 1 of the Annex to Decision 2000/147/EC.

Conditioned according to EN 13238.

Product detail Minimum mean density f15 (kg/m 3 ) Minimum overall thickness (mm) Class f16 (excluding floorings)
Structural timber Visual and machine graded structural timber with rectangular cross-sections shaped by sawing, planing or other methods or with round cross-sections 350 22 D-s2, d0
  1. Division

Annotations

Textual amendments

F1

Substituted by Commission Decision of 15 May 2007 amending Decision 2003/43/EC establishing the classes of reaction-to-fire performance for certain construction products as regards wood-based panels (notified under document number C(2007) 2045) (Text with EEA relevance) (2007/348/EC).

F2

Inserted by Commission Decision of 7 August 2003 amending Decision 2003/43/EC establishing the classes of reaction-to-fire performance of certain construction products (notified under document number C(2003) 2592) (Text with EEA relevance) (2003/593/EC).

F3

Substituted by Commission Decision of 5 October 2006 amending Decision 2003/43/EC establishing the classes of reaction-to-fire performance for certain construction products as regards gypsum plasterboards (notified under document number C(2006) 4360) (Text with EEA relevance) (2006/673/EC).

Footnotes

f1

A vapour barrier with a thickness up to 0,4 mm and a mass up to 200 g/m 2 can be mounted in between the wood-based panel and a substrate if there are no air gaps in between.

f2

Class as provided for in Table 1 of the Annex to Decision 2000/147/EC.

f3

Class as provided for in Table 2 of the Annex to Decision 2000/147/EC.

f4

Mounted without an air gap directly against class A1 or A2-s1, d0 products with minimum density 10 kg/m 3 or at least class D-s2, d2 products with minimum density 400 kg/m 3 .

f5

Mounted with an air gap behind. The reverse face of the cavity shall be at least class A2-s1, d0 products with minimum density 10 kg/m 3 .

f6

A substrate of cellulose insulation material of at least class E may be included if mounted directly against the wood-based panel, but not for floorings.

f7

Veneered, phenol- and melamine-faced panels are included for class excl. floorings.

f8

Mounted with an air gap behind. The reverse face of the cavity shall be at least class D-s2, d2 products with minimum density 400 kg/m 3 .

f9

Determined according to EN ISO 536 and with no more than 5 % organic additive content.

f10

Classes as provided for in Table 1 of the Annex to Commission Decision 2000/147/EC.

f11

Either directly fixed (i.e. with no air gap) to a material having a reaction to fire of A2-s1, d0 or better and a density of at least 600 kg/m 3 , or mounted on a timber or metal batten support frame, with a non-ventilated (i.e. void open only at the top) air gap of at least 30 mm, the reverse face of the cavity so formed having a reaction to fire classification of A2-s1, d0 or better.

f12

Classes as provided for in Table 1 of the Annex to Decision 2000/147/EC.

f13

Complying with European Standard EN 438-7.

f14

Applies to all species covered by the product standards.

f15

Conditioned according to EN 13238.

f16

Classes as provided for in Table 1 of the Annex to Decision 2000/147/EC.