The table set out in this Annex lists the construction products which satisfy all of the requirements for the external fire performance without need for testing.

Table

CLASSES OF EXTERNAL FIRE PERFORMANCE FOR DOUBLE SKIN METAL FACED SANDWICH PANELS FOR ROOFS

Panels with a profiled external metal facing incorporating:

  • minimum thickness 0,4 mm for facings of steel and stainless steel;

  • minimum thickness 0,9 mm for facings of aluminium;

  • at each longitudinal joint between two panels an overlap of the external metal facing extending across the crown and a minimum 15 mm down the opposite face of the crown, or a metal cover cap completely covering the joint crown, or a raised standing metal seam along the joint;

  • at each transverse joint between two panels an overlap of the external metal facing of at least 75 mm;

  • a protective weather coating comprising a liquid applied PVC paint of maximum nominal dry film thickness 0,200 mm, a PCS of not greater than 8,0 MJ/m2 and a maximum dry mass of 300 g/m2;

    or any thin paint coating less than the above;

  • minimum reaction to fire classification of D-s3, d0 without edge protection in accordance with EN 13501-1.

Class as provided for in the table of the Annex to Decision 2001/671/EC.

Symbols used: PUR = polyurethane; MW = mineral wool; PVC = polyvinyl chloride; PCS = gross calorific potential.

Productf1 Product detailCore material with minimum densityClassf2
Steel, stainless steel or aluminium faced sandwich panels for roofsIn accordance with EN 14509

PUR 35 kg/m3

or

BROOF (t1)

MW (lamellas) 80 kg/m3

or

BROOF (t2)
MW (full width boards) 110 kg/m3 BROOF (t3)

Annotations

Footnotes

f1

Panels with a profiled external metal facing incorporating:

  • minimum thickness 0,4 mm for facings of steel and stainless steel;

  • minimum thickness 0,9 mm for facings of aluminium;

  • at each longitudinal joint between two panels an overlap of the external metal facing extending across the crown and a minimum 15 mm down the opposite face of the crown, or a metal cover cap completely covering the joint crown, or a raised standing metal seam along the joint;

  • at each transverse joint between two panels an overlap of the external metal facing of at least 75 mm;

  • a protective weather coating comprising a liquid applied PVC paint of maximum nominal dry film thickness 0,200 mm, a PCS of not greater than 8,0 MJ/m2 and a maximum dry mass of 300 g/m2;

    or any thin paint coating less than the above;

  • minimum reaction to fire classification of D-s3, d0 without edge protection in accordance with EN 13501-1.

f2

Class as provided for in the table of the Annex to Decision 2001/671/EC.