Division 2 Efficiency in cooling mode (EER)

United Kingdom

Original text. Later amendments are not shown.

If the heat pump is reversible and can cool, then the efficiency of the heat pump unit shall exceed the following minimum requirements of the energy efficiency ratio (EER) in cooling mode.

Type of heat pump:Outdoor unit [°C]Indoor unit [°C]Min. EERMin. EERMin. PER
Electric heat pumpGas heat pump
air/air

Inlet dry bulb: 35

Inlet wet bulb: 24

Inlet dry bulb: 27

Inlet wet bulb: 19

3,21,411,3
air/water

Inlet dry bulb: 35

Inlet wet bulb: —

Inlet temperature: 23

Outlet temperature: 18

2,20,970,9

Inlet temperature: 12

Outlet temperature: 7

2,20,970,9
brine/air

Inlet temp: 30

Outlet temp: 35

Inlet dry bulb: 27

Inlet wet bulb: 19 max

3,31,451,3
brine/water

Inlet temp: 30

Outlet temp: 35

Inlet temperature: 23

Outlet temperature: 18

3,01,321,2

Inlet temperature: 12

Outlet temperature: 7

3,01,321,2
water/water

Inlet temp: 30

Outlet temp: 35

Inlet temperature: 23

Outlet temperature: 18

3,21,411,3

Inlet temperature: 12

Outlet temperature: 7

3,21,411,3
water/air

Inlet temp: 30

Outlet temp: 35

Inlet dry bulb: 27

Inlet wet bulb: 19

4,41,931,8

Assessment and verification: Testing shall be performed in accordance to EN 14 511:2004; for gas absorption heat pumps in accordance with EN12309-2:2000. The test shall be performed at the full capacity of the heat pump in question, at the conditions specified in the table. An independent test laboratory accredited for the stated testing shall verify the given values. Heat pumps which are certified in the Eurovent certification programme or DACH certification programme, or another programme approved by the competent body, do not require additional testing by an independent laboratory for the given values. The test reports shall be submitted with the application.