Division 32
United Kingdom
BAT is to carry out monitoring and measurements of process parameters and emissions on a regular basis and to monitor emissions in accordance with the relevant EN standards or, if EN standards are not available, ISO, national or other international standards that ensure the provision of data of an equivalent scientific quality, including the following:
| Technique | Applicability | |
|---|---|---|
| a | Continuous measurements of process parameters demonstrating the process stability, such as temperature, O2 content, pressure, flow rate and CO emissions | Applicable to kiln processes |
| b | Monitoring and stabilising of critical process parameters, e.g. fuel feed, regular dosage and excess oxygen | |
| c | Continuous or periodic measurements of dust, NOx, SOx, CO emissions and NH3 emissions when SNCR is applied | Applicable to kiln processes |
| d | Continuous or periodic measurements of HCl and HF emissions in case wastes are co-incinerated | Applicable to kiln processes |
| e | Continuous or periodic measurements of TOC emissions or continuous measurements in case wastes are co-incinerated | Applicable to kiln processes |
| f | Periodic measurements of PCDD/F and metal emissions | Applicable to kiln processes |
| g | Continuous or periodic measurements of dust emissions | Applicable to non-kiln processes For small sources (<10 000 Nm3/h) the frequency of the measurements should be based on a maintenance management system |