Division 2.2.1 Energy efficiency
United Kingdom
Table 8
BAT-associated energy efficiency levels (BAT-AEELs) for the combustion of solid biomass and/or peat
| These BAT-AEELs do not apply in the case of units operated < 1 500 h/yr. | ||||
| In the case of CHP units, only one of the two BAT-AEELs ‘Net electrical efficiency’ or ‘Net total fuel utilisation’ applies, depending on the CHP unit design (i.e. either more oriented towards electricity generation or towards heat generation). | ||||
| The lower end of the range may correspond to cases where the achieved energy efficiency is negatively affected (up to four percentage points) by the type of cooling system used or the geographical location of the unit. | ||||
| These levels may not be achievable if the potential heat demand is too low. | ||||
| These BAT-AEELs do not apply to plants generating only electricity. | ||||
| The lower end of the range may be down to 32 % in the case of units of < 150 MWth burning high-moisture biomass fuels. | ||||
| Type of combustion unit | BAT-AEELsf1 f2 | |||
|---|---|---|---|---|
| Net electrical efficiency (%)f3 | Net total fuel utilisation (%)f4 f5 | |||
| New unitf6 | Existing unit | New unit | Existing unit | |
| Solid biomass and/or peat boiler | 33,5–to > 38 | 28–38 | 73–99 | 73–99 |
Annotations
Footnotes
- f1
-
These BAT-AEELs do not apply in the case of units operated < 1 500 h/yr.
- f2
-
In the case of CHP units, only one of the two BAT-AEELs ‘Net electrical efficiency’ or ‘Net total fuel utilisation’ applies, depending on the CHP unit design (i.e. either more oriented towards electricity generation or towards heat generation).
- f3
-
The lower end of the range may correspond to cases where the achieved energy efficiency is negatively affected (up to four percentage points) by the type of cooling system used or the geographical location of the unit.
- f4
-
These levels may not be achievable if the potential heat demand is too low.
- f5
-
These BAT-AEELs do not apply to plants generating only electricity.
- f6
-
The lower end of the range may be down to 32 % in the case of units of < 150 MWth burning high-moisture biomass fuels.