Division BAT 33 In order to prevent or reduce emissions of CO and volatile organic compounds to air from the combustion of HFO and/or gas oil in reciprocating engines, BAT is to use one or both of the techniques given below.
United Kingdom
| Technique | Description | Applicability | |
|---|---|---|---|
| a. | Combustion optimisation | Generally applicable | |
| b. | Oxidation catalysts | See descriptions in Section 8.3 | Not applicable to combustion plants operated < 500 h/yr. The applicability may be limited by the sulphur content of the fuel |
Table 18
BAT-associated emission levels (BAT-AELs) for NOX emissions to air from the combustion of HFO and/or gas oil in reciprocating engines
| These BAT-AELs do not apply to plants operated < 1 500 h/yr or to plants that cannot be fitted with secondary abatement techniques. | ||||
| The BAT-AEL range is 1 150–1 900 mg/Nm3 for plants operated < 1 500 h/yr and for plants that cannot be fitted with secondary abatement techniques. | ||||
| For plants operated < 500 h/yr, these levels are indicative. | ||||
| For plants including units of < 20 MWth combusting HFO, the higher end of the BAT-AEL range applying to those units is 225 mg/Nm3. | ||||
| Combustion plant total rated thermal input(MWth) | BAT-AELs (mg/Nm3) | |||
|---|---|---|---|---|
| Yearly average | Daily average or average over the sampling period | |||
| New plant | Existing plantf1 | New plant | Existing plantf2 f3 | |
| ≥ 50 | 115–190f4 | 125–625 | 145–300 | 150–750 |
As an indication, for existing combustion plants burning only HFO and operated ≥ 1 500 h/yr or new combustion plants burning only HFO,
-
the yearly average CO emission levels will generally be 50–175 mg/Nm3,
-
the average over the sampling period for TVOC emission levels will generally be 10–40 mg/Nm3.
Annotations
Footnotes
- f1
-
These BAT-AELs do not apply to plants operated < 1 500 h/yr or to plants that cannot be fitted with secondary abatement techniques.
- f2
-
The BAT-AEL range is 1 150–1 900 mg/Nm3 for plants operated < 1 500 h/yr and for plants that cannot be fitted with secondary abatement techniques.
- f3
-
For plants operated < 500 h/yr, these levels are indicative.
- f4
-
For plants including units of < 20 MWth combusting HFO, the higher end of the BAT-AEL range applying to those units is 225 mg/Nm3.