Division BAT 71 In order to reduce emissions of volatile organic compounds and polychlorinated dibenzo-dioxins and -furans to air from the co-incineration of waste with biomass, peat, coal and/or lignite, BAT is to use a combination of the techniques given in BAT 6, BAT 26 and below.
United Kingdom
| Technique | Description | Applicability | |
|---|---|---|---|
| a. | Activated carbon injection | See description in Section 8.5. This process is based on the adsorption of pollutant molecules by the activated carbon | Generally applicable |
| b. | Rapid quenching using wet scrubbing/flue-gas condenser | See description of wet scrubbing/flue-gas condenser in Section 8.4 | |
| c. | Selective catalytic reduction (SCR) | See description in Section 8.3. The SCR system is adapted and larger than an SCR system only used for NOX reduction | See applicability in BAT 20 and in BAT 24 |
Table 41
BAT-associated emission levels (BAT-AELs) for PCDD/F and TVOC emissions to air from the co-incineration of waste with biomass, peat, coal and/or lignite
| Type of combustion plant | BAT-AELs | ||
|---|---|---|---|
| PCDD/F (ng I-TEQ/Nm3) | TVOC (mg/Nm3) | ||
| Average over the sampling period | Yearly average | Daily average | |
| Biomass-, peat-, coal- and/or lignite-fired combustion plant | < 0,01–0,03 | < 0,1–5 | 0,5–10 |