Division .13 The minimum number of fire extinguishers shall be as follows:F1
United Kingdom
- .1
in accommodation and service spaces:
the fire extinguishers shall be so located that no point in the space is more than 10 metres walking distance from an extinguisher;
- .2
an extinguisher suitable for use in high voltage areas shall be located in the proximity of any electric panel or subpanel having a power of 20 kW or more;
- .3
in galleys the extinguishers shall be so located that no point in the space is more than 10 metres walking distance from an extinguisher;
- .4
an extinguisher shall be located in the proximity of paint lockers store rooms containing readily flammable products;
- .5
at least one extinguisher shall be located on the navigating bridge and in each control station.