Division .4 As permitted by paragraphs .2.2 and .2.3 ducts shall be either:F1F2
United Kingdom
- .1.1
constructed of steel having a thickness of at least 3 mm for ducts with a free cross-sectional area of less than 0,075 m 2 , at least 4 mm for ducts with a free cross-sectional area of between 0,075 m 2 and 0,45 m 2 , and at least 5 mm for ducts with a free cross-sectional area of over 0,45 m 2 ;
- .1.2
suitably supported and stiffened;
- .1.3
fitted with automatic fire dampers close to the boundaries penetrated; and
- .1.4
insulated to ‘ A-60 ’ class standard from the boundaries of the spaces they serve to a point at least 5 m beyond each fire damper;
or
- .2.1
constructed of steel in accordance with paragraphs .2.4.1.1 and .2.4.1.2; and
- .2.2
insulated to ‘ A-60 ’ class standard throughout the spaces they pass through, except for ducts that pass through spaces of category (9) or (10) as defined in Regulation II-2/B/4.2.2.