Division 2
United Kingdom
Emission limit values (mg/Nm3) for SO2 for combustion plants using solid or liquid fuels with the exception of gas turbines and gas engines
| Total rated thermal input (MW) | Coal and lignite and other solid fuels | Biomass | Peat | Liquid fuels |
|---|---|---|---|---|
| 50-100 | 400 | 200 | 300 | 350 |
| 100-300 | 200 | 200 | 300 250 in case of fluidised bed combustion | 200 |
| > 300 | 150 200 in case of circulating or pressurised fluidised bed combustion | 150 | 150 200 in case of fluidised bed combustion | 150 |