Division 6 Conditions for testing solar devices
United Kingdom
The solar collector, solar hot water storage tank and pump in the collector loop (if applicable) shall be tested separately. Where the solar collector and solar hot water storage tank cannot be tested separately, they shall be tested in combination.
The results shall be used for the calculations of Qnonsol for the load profiles M, L, XL and XXL under the average climate conditions set out in Tables 4 and 5 and Qaux .
Table 4
Average daytime temperature [°C]
| January | February | March | April | May | June | July | August | September | October | November | December | |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Average climate conditions | + 2,8 | + 2,6 | + 7,4 | + 12,2 | + 16,3 | + 19,8 | + 21,0 | + 22,0 | + 17,0 | + 11,9 | + 5,6 | + 3,2 |
| Colder climate conditions | – 3,8 | – 4,1 | – 0,6 | + 5,2 | + 11,0 | + 16,5 | + 19,3 | + 18,4 | + 12,8 | + 6,7 | + 1,2 | – 3,5 |
| Warmer climate conditions | + 9,5 | + 10,1 | + 11,6 | + 15,3 | + 21,4 | + 26,5 | + 28,8 | + 27,9 | + 23,6 | + 19,0 | + 14,5 | + 10,4 |
Table 5
Average global solar irradiance [W/m2]
| January | February | March | April | May | June | July | August | September | October | November | December | |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Average climate conditions | 70 | 104 | 149 | 192 | 221 | 222 | 232 | 217 | 176 | 129 | 80 | 56 |
| Colder climate conditions | 22 | 75 | 124 | 192 | 234 | 237 | 238 | 181 | 120 | 64 | 23 | 13 |
| Warmer climate conditions | 128 | 137 | 182 | 227 | 248 | 268 | 268 | 263 | 243 | 175 | 126 | 109 |
Table 6
Standard rating conditions for heat pump water heaters, temperatures in dry bulb air temperature (wet bulb air temperature in brackets)
| Heat source | Outdoor air | Indoor air | Exhaust air | Brine | Water | ||
|---|---|---|---|---|---|---|---|
| Climate conditions | Average climate conditions | Colder climate conditions | Warmer climate conditions | Not applicable | All climate conditions | ||
| Temperature | + 7 °C (+ 6 °C) | + 2 °C (+ 1 °C) | + 14 °C (+ 13 °C) | + 20 °C (maximum + 15 °C) | + 20 °C (+ 12 °C) | 0 °C (inlet)/– 3 °C (outlet) | + 10 °C (inlet)/+ 7 °C (outlet) |
Table 7
Maximum ventilation exhaust air available [m3/h], at a temperature of 20 °C and with humidity of 5,5 g/m3
| Declared load profile | XXS | XS | S | M | L | XL | XXL |
|---|---|---|---|---|---|---|---|
| Maximum ventilation exhaust air available | 109 | 128 | 128 | 159 | 190 | 870 | 1 021 |