Division 5 REQUIREMENTS FOR PRODUCT INFORMATION

United Kingdom

Original text. Later amendments are not shown.

From 26 September 2015 the following product information on heaters shall be provided:

  1. (a)

    the instruction manuals for installers and end-users, and free access websites of manufacturers, their authorised representatives and importers shall contain the following elements:

    • for boiler space heaters, boiler combination heaters and cogeneration space heaters, the technical parameters set out in Table 1, measured and calculated in accordance with Annex III;

    • for heat pump space heaters and heat pump combination heaters, the technical parameters set out in Table 2, measured and calculated in accordance with Annex III;

    • any specific precautions that shall be taken when the heater is assembled, installed or maintained;

    • for type B1 boilers and type B1 combination boilers, their characteristics and the following standard text: ‘This natural draught boiler is intended to be connected only to a flue shared between multiple dwellings in existing buildings that evacuates the residues of combustion to the outside of the room containing the boiler. It draws the combustion air directly from the room and incorporates a draught diverter. Due to lower efficiency, any other use of this boiler shall be avoided and would result in higher energy consumption and higher operating costs.’;

    • for heat generators designed for heaters, and heater housings to be equipped with such heat generators, their characteristics, the requirements for assembly, to ensure compliance with the ecodesign requirements for heaters and, where appropriate, the list of combinations recommended by the manufacturer;

    • information relevant for disassembly, recycling and/or disposal at end-of-life;

  2. (b)

    the technical documentation for the purposes of conformity assessment pursuant to Article 4 shall contain the following elements:

    • the elements specified in point (a);

    • for heat pump space heaters and heat pump combination heaters where the information relating to a specific model comprising a combination of indoor and outdoor units has been obtained by calculation on the basis of design and/or extrapolation from other combinations, the details of such calculations and/or extrapolations, and of any tests undertaken to verify the accuracy of the calculations, including details of the mathematical model for calculating the performance of such combinations and details of the measurements taken to verify this model;

  3. (c)

    the following information shall be durably marked on the heater:

    • if applicable, ‘type B1 boiler’ or ‘type B1 combination boiler’;

    • for cogeneration space heaters, the electrical capacity.

Table 1

Information requirements for boiler space heaters, boiler combination heaters and cogeneration space heaters

High-temperature regime means 60 °C return temperature at heater inlet and 80 °C feed temperature at heater outlet.

Low temperature means for condensing boilers 30 °C, for low-temperature boilers 37 °C and for other heaters 50 °C return temperature (at heater inlet).

Model(s): [information identifying the model(s) to which the information relates]
Condensing boiler: [yes/no]
Low-temperaturef1 boiler: [yes/no]
B1 boiler: [yes/no]
Cogeneration space heater: [yes/no]If yes, equipped with a supplementary heater: [yes/no]
Combination heater: [yes/no]
Item Symbol Value Unit Item Symbol Value Unit
Rated heat output Prated xkW Seasonal space heating energy efficiency ηs x%
For boiler space heaters and boiler combination heaters: Useful heat outputFor boiler space heaters and boiler combination heaters: Useful efficiency
At rated heat output and high-temperature regimef2 P4 x,xkWAt rated heat output and high-temperature regime η4 x,x%
At 30 % of rated heat output and low-temperature regime P1 x,xkWAt 30 % of rated heat output and low-temperature regime η1 x,x%
For cogeneration space heaters: Useful heat outputFor cogeneration space heaters: Useful efficiency
At rated heat output of cogeneration space heater with supplementary heater disabled PCHP100 + Sup0 x,xkWAt rated heat output of cogeneration space heater with supplementary heater disabled ηCHP100 + Sup0 x,x%
At rated heat output of cogeneration space heater with supplementary heater enabled PCHP100 + Sup100 x,xkWAt rated heat output of cogeneration space heater with supplementary heater enabled ηCHP100 + Sup100 x,x%
For cogeneration space heaters: Electrical efficiencySupplementary heater
At rated heat output of cogeneration space heater with supplementary heater disabled ηel,CHP100 + Sup0 x,x%Rated heat output Psup x,xkW
At rated heat output of cogeneration space heater with supplementary heater enabled ηel,CHP100 + Sup100 x,x%Type of energy input
Auxiliary electricity consumptionOther items
At full load elmax x,xxxkWStandby heat loss Pstby x,xxxkW
At part load elmin x,xxxkWIgnition burner power consumption Pign x,xxxkW
In standby mode PSB x,xxxkWEmissions of nitrogen oxides NOx xmg/kWh
For combination heaters:
Declared load profile Water heating energy efficiency ηwh x%
Daily electricity consumption Qelec x,xxxkWhDaily fuel consumption Qfuel x,xxxkWh
Contact detailsName and address of the manufacturer or its authorised representative.

Table 2

Information requirements for heat pump space heaters and heat pump combination heaters

For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj).

If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.

Model(s): [information identifying the model(s) to which the information relates]
Air-to-water heat pump: [yes/no]
Water-to-water heat pump: [yes/no]
Brine-to-water heat pump: [yes/no]
Low-temperature heat pump: [yes/no]
Equipped with a supplementary heater: [yes/no]
Heat pump combination heater: [yes/no]
Parameters shall be declared for medium-temperature application, except for low-temperature heat pumps. For low-temperature heat pumps, parameters shall be declared for low-temperature application.
Parameters shall be declared for average climate conditions.
Item Symbol Value Unit Item Symbol Value Unit
Rated heat output f3 Prated xkW Seasonal space heating energy efficiency ηs x%
Declared capacity for heating for part load at indoor temperature 20 °C and outdoor temperature Tj Declared coefficient of performance or primary energy ratio for part load at indoor temperature 20 °C and outdoor temperature Tj
Tj = – 7 °C Pdh x,xkW Tj = – 7 °C COPd or PERd x,xx or x,x– or %
Tj = + 2 °C Pdh x,xkW Tj = + 2 °C COPd or PERd x,xx or x,x– or %
Tj = + 7 °C Pdh x,xkW Tj = + 7 °C COPd or PERd x,xx or x,x– or %
Tj = + 12 °C Pdh x,xkW Tj = + 12 °C COPd or PERd x,xx or x,x– or %
Tj = bivalent temperature Pdh x,xkW Tj = bivalent temperature COPd or PERd x,xx or x,x– or %
Tj = operation limit temperature Pdh x,xkW Tj = operation limit temperature COPd or PERd x,xx or x,x– or %
For air-to-water heat pumps: Tj = – 15 °C (if TOL < – 20 °C) Pdh x,xkWFor air-to-water heat pumps: Tj = – 15 °C (if TOL < – 20 °C) COPd or PERd x,xx or x,x– or %
Bivalent temperature Tbiv x°CFor air-to-water heat pumps: Operation limit temperature TOL x°C
Cycling interval capacity for heating Pcych x,xkWCycling interval efficiency COPcyc or PERcyc x,xx or x,x– or %
Degradation co-efficientf4 Cdh x,x—Heating water operating limit temperature WTOL x°C
Power consumption in modes other than active modeSupplementary heater
Off mode POFF x,xxxkWRated heat output Psup x,xkW
Thermostat-off mode PTO x,xxxkW
Standby mode PSB x,xxxkWType of energy input
Crankcase heater mode PCK x,xxxkW
Other items
Capacity controlfixed/variableFor air-to-water heat pumps: Rated air flow rate, outdoors—xm3/h
Sound power level, indoors/outdoors LWA x/xdBFor water-/brine-to-water heat pumps: Rated brine or water flow rate, outdoor heat exchanger—xm3/h
Emissions of nitrogen oxides NOx xmg/kWh
For heat pump combination heater:
Declared load profile x Water heating energy efficiency ηwh x%
Daily electricity consumption Qelec x,xxxkWhDaily fuel consumption Qfuel x,xxxkWh
Contact detailsName and address of the manufacturer or its authorised representative.

Annotations

Footnotes

f1

Low temperature means for condensing boilers 30 °C, for low-temperature boilers 37 °C and for other heaters 50 °C return temperature (at heater inlet).

f2

High-temperature regime means 60 °C return temperature at heater inlet and 80 °C feed temperature at heater outlet.

f3

For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj).

f4

If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.