Division 1 REQUIREMENTS FOR ENERGY EFFICIENCY
United Kingdom
- (a)
From 1 July 2016, the seasonal energy performance ratio (SEPR) of process chillers shall not fall below the following values:
Heat transfer medium at the condensing side Operating temperature Rated cooling capacityPA Minimum SEPR value Air Medium PA ≤ 300 kW 2,24 PA > 300 kW 2,80 Low PA ≤ 200 kW 1,48 PA > 200 kW 1,60 Water Medium PA ≤ 300 kW 2,86 PA > 300 kW 3,80 Low PA ≤ 200 kW 1,82 PA > 200 kW 2,10 - (b)
From 1 July 2018, the seasonal energy performance ratio (SEPR) of process chillers shall not fall below the following values:
Heat transfer medium at the condensing side Operating temperature Rated cooling capacityPA Minimum SEPR value Air Medium PA ≤ 300 kW 2,58 PA > 300 kW 3,22 Low PA ≤ 200 kW 1,70 PA > 200 kW 1,84 Water Medium PA ≤ 300 kW 3,29 PA > 300 kW 4,37 Low PA ≤ 200 kW 2,09 PA > 200 kW 2,42 - (c)
For process chillers intended to be charged with a refrigerant fluid with a global warming potential lower than 150, SEPR values can be lower than the values indicated in points 1(a) and (b) by a maximum of 10 %.