Division 2 At the date of entry into force of this Regulation, the best available technology on the market for condensing units in terms of rated coefficient of performance and seasonal energy performance ratio was identified as follows:

United Kingdom

Original text. Later amendments are not shown.

Operating temperatureRated capacity PA Applicable ratioBenchmark value
Medium0,2 kW ≤ PA ≤ 1 kWCOP1,9
1 kW < PA ≤ 5 kWCOP2,3
5 kW < PA ≤ 20 kWSEPR3,6
20 kW < PA ≤ 50 kWSEPR3,5
Low0,1 kW ≤ PA ≤ 0,4 kWCOP1,0
0,4 kW < PA ≤ 2 kWCOP1,3
2 kW < PA ≤ 8 kWSEPR2,0
8 kW < PA ≤ 20 kWSEPR2,0