Division 3 At the date of entry into force of this Regulation, the best available technology on the market for process chillers in terms of seasonal energy performance ratio was identified as follows:
United Kingdom
| Heat transfer medium at the condensing side | Operating temperature | Rated cooling capacityPA | Minimum SEPR value |
|---|---|---|---|
| Air | Medium | PA ≤ 300 kW | 3,4 |
| PA > 300 kW | 3,7 | ||
| Low | PA ≤ 200 kW | 1,9 | |
| PA > 200 kW | 1,95 | ||
| Water | Medium | PA ≤ 300 kW | 4,3 |
| PA > 300 kW | 4,5 | ||
| Low | PA ≤ 200 kW | 2,3 | |
| PA > 200 kW | 2,7 |