Division 3 At the date of entry into force of this Regulation, the best available technology on the market for process chillers in terms of seasonal energy performance ratio was identified as follows:

United Kingdom

Original text. Later amendments are not shown.

Heat transfer medium at the condensing sideOperating temperatureRated cooling capacityPA Minimum SEPR value
AirMedium PA ≤ 300 kW3,4
PA > 300 kW3,7
Low PA ≤ 200 kW1,9
PA > 200 kW1,95
WaterMedium PA ≤ 300 kW4,3
PA > 300 kW4,5
Low PA ≤ 200 kW2,3
PA > 200 kW2,7