Division 2 Requirements for product information
United Kingdom
From 1 January 2020 the following product information on solid fuel boilers shall be provided:
- (a)
in the instruction manuals for installers and end-users, and on the free-access websites of manufacturers, their authorised representatives and importers:
- (1)
the information included in Table 1, with its technical parameters measured and calculated in accordance with Annex III and showing the number of significant figures indicated in the table;
- (2)
any specific precautions to be taken when the solid fuel boiler is assembled, installed or maintained;
- (3)
instruction on the proper way to operate the solid fuel boiler and on the quality requirements for the preferred fuel and any other suitable fuels;
- (4)
for solid fuel heat generators designed for solid fuel boilers, and solid fuel boiler housings to be equipped with such heat generators, their characteristics, the requirements for assembly (to ensure compliance with the ecodesign requirements for solid fuel boilers) and, where appropriate, the list of combinations recommended by the manufacturer;
- (1)
- (b)
on a part for professionals of the free-access websites of manufacturers, their authorised representatives and importers: information relevant to disassembly, recycling and disposal at end-of-life;
- (c)
in the technical documentation for the purposes of conformity assessment pursuant to Article 4:
- (1)
the information listed in points (a) and (b);
- (2)
a list of all equivalent models, if applicable;
- (3)
where the preferred fuel or any other suitable fuel is other woody biomass, non-woody biomass, other fossil fuel or other blend of biomass and fossil fuel as referred to in Table 1, a description of the fuel sufficient for its unambiguous identification and the technical standard or specification of the fuel, including the measured moisture content, and the measured ash content, and for other fossil fuel also the measured volatile content of the fuel;
- (1)
- (d)
the electrical capacity, marked in a permanent manner on the solid fuel cogeneration boiler.
The information referred to in point (c) may be merged with the technical documentation provided in accordance with measures under Directive 2010/30/EU.
Table 1
Information requirements for solid fuel boilers
| Tank volume = 45 × Pr × (1 – 2,7/Pr ) or 300 litres, whichever is higher, with Pr indicated in kW | |||||||||||||
| Tank volume = 20 × Pr with Pr indicated in kW | |||||||||||||
| For the preferred fuel Pn equals Pr | |||||||||||||
| PM = particulate matter, OGC = organic gaseous compounds, CO = carbon monoxide, NOx = nitrogen oxides | |||||||||||||
| Model identifier(s) | |||||||||||||
| Stoking mode: [Manual: the boiler should be operated with a hot water storage tank of a volume of at least xf1 litre/Automatic: it is recommended that the boiler be operated with a hot water storage tank of a volume of at least xf2 litre] | |||||||||||||
| Condensing boiler: [yes/no] | |||||||||||||
| Solid fuel cogeneration boiler: [yes/no] | Combination boiler: [yes/no] | ||||||||||||
| Fuel | Preferred fuel (only one): | Other suitable fuel(s): | ηs [x%]: | Seasonal space heating emissionsf3 | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| PM | OGC | CO | NOx | ||||||||||
| [x] mg/m3 | |||||||||||||
| Log wood, moisture content ≤ 25 % | [yes/no] | [yes/no] | |||||||||||
| Chipped wood, moisture content 15-35 % | [yes/no] | [yes/no] | |||||||||||
| Chipped wood, moisture content > 35 % | [yes/no] | [yes/no] | |||||||||||
| Compressed wood in the form of pellets or briquettes | [yes/no] | [yes/no] | |||||||||||
| Sawdust, moisture content ≤ 50 % | [yes/no] | [yes/no] | |||||||||||
| Other woody biomass | [yes/no] | [yes/no] | |||||||||||
| Non-woody biomass | [yes/no] | [yes/no] | |||||||||||
| Bituminous coal | [yes/no] | [yes/no] | |||||||||||
| Brown coal (including briquettes) | [yes/no] | [yes/no] | |||||||||||
| Coke | [yes/no] | [yes/no] | |||||||||||
| Anthracite | [yes/no] | [yes/no] | |||||||||||
| Blended fossil fuel briquettes | [yes/no] | [yes/no] | |||||||||||
| Other fossil fuel | [yes/no] | [yes/no] | |||||||||||
| Blended biomass (30-70 %)/fossil fuel briquettes | [yes/no] | [yes/no] | |||||||||||
| Other blend of biomass and fossil fuel | [yes/no] | [yes/no] | |||||||||||
| Characteristics when operating with the preferred fuel only: | |||||||||||||
| Item | Symbol | Value | Unit | Item | Symbol | Value | Unit | ||||||
| Useful heat output | Useful efficiency | ||||||||||||
| At rated heat output | Pn f4 | x,x | kW | At rated heat output | ηn | x,x | % | ||||||
| At [30 %/50 %] of rated heat output, if applicable | Pp | [x,x/N.A.] | kW | At [30 %/50 %] of rated heat output, if applicable | ηp | [x,x/N.A.] | % | ||||||
| For solid fuel cogeneration boilers: Electrical efficiency | Auxiliary electricity consumption | ||||||||||||
| At rated heat output | elmax | x,xxx | kW | ||||||||||
| At rated heat output | ηel,n | x,x | % | At [30 %/50 %] of rated heat output, if applicable | elmin | [x,xxx/N.A.] | kW | ||||||
| Of incorporated secondary emission abatement equipment, if applicable | [x,xxx/N.A.] | kW | |||||||||||
| In standby mode | PSB | x,xxx | kW | ||||||||||
| Contact details | Name and address of the manufacturer or its authorised representative. | ||||||||||||
Annotations
Footnotes
- f1
-
Tank volume = 45 × Pr × (1 – 2,7/Pr ) or 300 litres, whichever is higher, with Pr indicated in kW
- f2
-
Tank volume = 20 × Pr with Pr indicated in kW
- f3
-
PM = particulate matter, OGC = organic gaseous compounds, CO = carbon monoxide, NOx = nitrogen oxides
- f4
-
For the preferred fuel Pn equals Pr