Division 3 Seasonal energy performance ratio of high temperature process chillers:
United Kingdom
- (a)
From 1 January 2018, the seasonal energy performance ratio of high temperature process chillers shall not fall below the values in Table 5:
Table 5 First tier seasonal energy performance ratio of high temperature process chillers To be declared in the relevant tables in this Annex and in the technical documentation rounded to two decimal places.
Heat transfer medium at the condensing side Rated refrigeration capacity Minimum SEPR f1 value Air PA < 400 kW 4,5 PA ≥ 400 kW 5,0 Water PA < 400 kW 6,5 400 kW ≤ PA < 1 500 kW 7,5 PA ≥ 1 500 kW 8,0 - (b)
From 1 January 2021, the seasonal energy performance ratio of high temperature process chillers shall not fall below the values in Table 6:
Table 6 Second tier seasonal energy performance ratio of high temperature process chillers To be declared in the relevant tables in this Annex and in the technical documentation rounded to two decimal places.
Heat transfer medium at the condensing side Rated refrigeration capacity Minimum SEPR f2 value Air PA < 400 kW 5,0 PA ≥ 400 kW 5,5 Water PA < 400 kW 7,0 400 kW ≤ PA < 1 500 kW 8,0 PA ≥ 1 500 kW 8,5
Annotations
Footnotes
- f1
-
To be declared in the relevant tables in this Annex and in the technical documentation rounded to two decimal places.
- f2
-
To be declared in the relevant tables in this Annex and in the technical documentation rounded to two decimal places.