Division 3 Seasonal energy performance ratio of high temperature process chillers:

United Kingdom

Original text. Later amendments are not shown.

  1. (a)

    From 1 January 2018, the seasonal energy performance ratio of high temperature process chillers shall not fall below the values in Table 5:

    Table 5
    First tier seasonal energy performance ratio of high temperature process chillers

    To be declared in the relevant tables in this Annex and in the technical documentation rounded to two decimal places.

    Heat transfer medium at the condensing sideRated refrigeration capacityMinimum SEPR f1 value
    AirPA < 400 kW4,5
    PA ≥ 400 kW5,0
    WaterPA < 400 kW6,5
    400 kW ≤ PA < 1 500 kW7,5
    PA ≥ 1 500 kW8,0
  2. (b)

    From 1 January 2021, the seasonal energy performance ratio of high temperature process chillers shall not fall below the values in Table 6:

    Table 6
    Second tier seasonal energy performance ratio of high temperature process chillers

    To be declared in the relevant tables in this Annex and in the technical documentation rounded to two decimal places.

    Heat transfer medium at the condensing sideRated refrigeration capacityMinimum SEPR f2 value
    AirPA < 400 kW5,0
    PA ≥ 400 kW5,5
    WaterPA < 400 kW7,0
    400 kW ≤ PA < 1 500 kW8,0
    PA ≥ 1 500 kW8,5

Annotations

Footnotes

f1

To be declared in the relevant tables in this Annex and in the technical documentation rounded to two decimal places.

f2

To be declared in the relevant tables in this Annex and in the technical documentation rounded to two decimal places.