  1. (a)

    From 1 January 2018, the instruction manuals for installers and end-users, and free access websites of manufacturers, their authorised representatives and importers shall provide the following product information:

    1. (1)

      for warm air heaters, the information set out in Table 9 of this Annex, measured and calculated in accordance with Annex III;

    2. (2)

      for comfort chillers, the information set out in Table 10 of this Annex, measured and calculated in accordance with Annex III;

    3. (3)

      for air-to-air air conditioners, the information set out in Table 11 of this Annex, measured and calculated in accordance with Annex III;

    4. (4)

      for water/brine-to-air air conditioners, the information set out in Table 12 of this Annex, measured and calculated in accordance with Annex III;

    5. (5)

      for fan coil units, the information set out in Table 13 of this Annex, measured and calculated in accordance with Annex III;

    6. (6)

      for heat pumps, the information set out in Table 14 of this Annex, measured and calculated in accordance with Annex III;

    7. (7)

      for high temperature process chillers, the information set out in Table 15 of this Annex, measured and calculated in accordance with Annex III;

    8. (8)

      any specific precautions that must be taken when the product is assembled, installed or maintained;

    9. (9)

      for heat generators or cold generators designed for air heating or cooling products, and air heating or cooling product housings to be equipped with such heat or cold generators, their characteristics, the requirements for assembly, to ensure compliance with the ecodesign requirements for air heating or cooling products and, where appropriate, the list of combinations recommended by the manufacturer;

    10. (10)

      for multi-split heat pumps and multi-split air conditioners, a list of appropriate indoor units;

    11. (11)

      for B1, C2 and C4 warm air heaters the following standard text: ‘This warm air heater is intended to be connected only to a flue shared between multiple dwellings in existing buildings. Due to a lower efficiency, any other use of this warm air heater shall be avoided and would result in higher energy consumption and higher operating costs’.

  2. (b)

    From 1 January 2018, the instruction manuals for installers and end-users, and a part for professionals of the free-access websites of manufacturers, their authorised representatives and importers shall provide the following product information:

    1. (1)

      information relevant for disassembly, recycling and/or disposal at end-of-life.

  3. (c)

    The technical documentation for the purposes of conformity assessment pursuant to Article 4 shall contain the following elements:

    1. (1)

      the elements specified in point (a);

    2. (2)

      where the information relating to a specific model has been obtained by calculation on the basis of design, and/or extrapolation from other combinations, the technical documentation shall include details of such calculations and/or extrapolations, and of tests undertaken to verify the accuracy of the calculations undertaken, including details of the mathematical model for calculating performance of such combinations, and of measurements taken to verify this model, and a list of any other models where the information included in the technical documentation was obtained on the same basis.

  4. (d)

    The manufacturer, their authorised representatives and importers of comfort chillers, air-to-air and water/brine-to-air air conditioners, heat pumps and high temperature process chillers shall provide laboratories performing market surveillance checks, upon request, the necessary information on the setting of the unit, as applied for the establishment of declared capacities, SEER/EER, SCOP/COP, SEPR/COP values, where applicable, and provide contact information for obtaining such information.

Table 9
Information requirements for warm air heaters

Not required for electric warm air heaters.

From 26 September 2018.

Model(s): Information to identify the model(s) to which the information relates:
B1 warm air heater: [yes/no]
C2 warm air heater: [yes/no]
C4 warm air heater: [yes/no]
Type of fuel: [gas/liquid/electricity]
ItemSymbolValueUnitItemSymbolValueUnit
CapacityUseful efficiency
Rated heating capacity Pated,h x,xkWUseful efficiency at rated heating capacityf1 ηnom x,x%
Minimum capacity Pmin x,xkWUseful efficiency at minimum capacity ηpl x,x%
Electric power consumption Other items
At rated heating capacity elmax x,xxxkWEnvelope loss factor Fenv x,x%
At minimal capacity elmin x,xxxkWIgnition burner power consumption Pign x,xkW
In standby mode elsb x,xxxkWEmissions of nitrogen oxides f2 NOx xmg/kWh input energy (GCV)
Emission efficiency ηs,flow x,x%
Seasonal space heating energy efficiency ηs,h x,x%
Contact detailsName and address of the manufacturer or of its authorised representative.
Table 10
Information requirements for comfort chillers

If Cdc is not determined by measurement then the default degradation coefficient of chillers shall be 0,9.

From 26 September 2018.

Model(s): Information to identify the model(s) to which the information relates:
Outdoor side heat exchanger of chiller: [select which: air or water/brine]
Indoor side heat exchanger chiller: [default: water]
Type: compressor driven vapour compression or sorption process
If applicable: driver of compressor: [electric motor or fuel driven, gaseous or liquid fuel, internal or external combustion engine]
ItemSymbolValueUnitItemSymbolValueUnit
Rated cooling capacity Prated,c x,xkWSeasonal space cooling energy efficiency ηs,c x,x%
Declared cooling capacity for part load at given outdoor temperatures Tj Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Tj = + 35 °C Pdc x,xkW Tj = + 35 °C EERd or GUEc,bin/AEFc,bin x,x%
Tj = + 30 °C Pdc x,xkW Tj = + 30 °C EERd or GUEc,bin/AEFc,bin x,x%
Tj = + 25 °C Pdc x,xkW Tj = + 25 °C EERd or GUEc,bin/AEFc,bin x,x%
Tj = + 20 °C Pdc x,xkW Tj = + 20 °C EERd or GUEc,bin/AEFc,bin x,x%
Degradation co-efficient for chillersf3 Cdc x,x—
Power consumption in modes other than ‘active mode’
Off mode POFF x,xxxkWCrankcase heater mode PCK x,xxxkW
Thermostat-off mode PTO x,xxxkWStandby mode PSB x,xxxkW
Other items
Capacity controlfixed/staged/variableFor air-to-water comfort chillers: air flow rate, outdoor measured—xm3/h
Sound power level, outdoor LWA x,x/x,xdBFor water/brine-to-water chillers: Rated brine or water flow rate, outdoor side heat exchanger—xm3/h
Emissions of nitrogen oxides (if applicable)NOx f4 xmg/kWh input GCV
GWP of the refrigerantkg CO2 eq (100 years)
Standard rating conditions used: [low temperature application/medium temperature application]
Contact detailsName and address of the manufacturer or of its authorised representative.
Table 11
Information requirements for air-to-air air conditioners

If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.

From 26 September 2018.

Where information relates to multi-split air conditioners, the test result and performance data may be obtained on the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.

Model(s): Information to identify the model(s) to which the information relates:
Outdoor side heat exchanger of air conditioner: [default: air]
Indoor side heat exchanger of air conditioner: [default: air]
Type: compressor driven vapour compression or sorption process
If applicable: driver of compressor: [electric motor or fuel driven, gaseous or liquid fuel, internal or external combustion engine]
ItemSymbolValueUnitItemSymbolValueUnit
Rated cooling capacity Prated,c x,xkWSeasonal space cooling energy efficiency ηs,c x,x%
Declared cooling capacity for part load at given outdoor temperatures Tj and indoor 27°/19 °C (dry/wet bulb)Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Tj = + 35 °C Pdc x,xkW Tj = + 35 °C EERd or GUEc,bin/AEFc,bin x,x%
Tj = + 30 °C Pdc x,xkW Tj = + 30 °C EERd or GUEc,bin/AEFc,bin x,x%
Tj = + 25 °C Pdc x,xkW Tj = + 25 °C EERd or GUEc,bin/AEFc,bin x,x%
Tj = + 20 °C Pdc x,xkW Tj = + 20 °C EERd or GUEc,bin/AEFc,bin x,x%
Degradation co-efficient for air conditionersf5 Cdc x,x—
Power consumption in modes other than ‘active mode’
Off mode POFF x,xxxkWCrankcase heater mode PCK x,xxxkW
Thermostat-off mode PTO x,xxxkWStandby mode PSB x,xxxkW
Other items
Capacity controlfixed/staged/variableFor air-to-air air conditioner: air flow rate, outdoor measured—xm3/h
Sound power level, outdoor LWA x,x/x,xdB
If engine driven: Emissions of nitrogen oxidesNOx f6 xmg/kWh fuel input GCV
GWP of the refrigerantkg CO2 eq (100 years)
Contact detailsName and address of the manufacturer or of its authorised representative.
Table 12
Information requirements for water/brine-to-air air conditioners

If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.

From 26 September 2018. Where information relates to multi-split air conditioners, the test result and performance data may be obtained on the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.

Model(s): Information to identify the model(s) to which the information relates:
Outdoor side heat exchanger of air conditioner: [default: water/brine]
Indoor side heat exchanger of air conditioner: [default: air]
Type: compressor driven vapour compression or sorption process
If applicable: driver of compressor: [electric motor or fuel driven, gaseous or liquid fuel, internal or external combustion engine]
ItemSymbolValueUnitItemSymbolValueUnit
Rated cooling capacity Prated,c x,xkWSeasonal space cooling energy efficiency ηs,c x,x%
Declared cooling capacity for part load at given outdoor temperatures Tj and indoor 27°/19 °C (dry/wet bulb)Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Outdoor temperature Tj cooling tower (inlet/outlet)ground coupled
Tj = + 35 °C30/3510/15 Pdc x,xkW Tj = + 35 °C EERd or GUEc,bin/AEFc,bin x,x%
Tj = + 30 °C26/*10/* Pdc x,xkW Tj = + 30 °C EERd or GUEc,bin/AEFc,bin x,x%
Tj = + 25 °C22/*10/* Pdc x,xkW Tj = + 25 °C EERd or GUEc,bin/AEFc,bin x,x%
Tj = + 20 °C18/*10/* Pdc x,xkW Tj = + 20 °C EERd or GUEc,bin/AEFc,bin x,x%
Degradation co-efficient for air conditionersf7 Cdc x,x—
Power consumption in modes other than ‘active mode’
Off mode POFF x,xxxkWCrankcase heater mode PCK x,xxxkW
Thermostat-off mode PTO x,xxxkWStandby mode PSB x,xxxkW
Other items
Capacity controlfixed/staged/variable
Sound power level, outdoor LWA x,x/x,xdBFor water/brine-to-air air conditioners: Rated brine or water flow rate, outdoor side heat exchanger—xm3/h

If engine driven

Emissions of nitrogen oxides (if applicable)

NOx f8 xmg/kWh fuel input GCV
GWP of the refrigerantkg CO2 eq (100 years)
Contact detailsName and address of the manufacturer or of its authorised representative.
Table 13
Information requirements for fan coil units
Information to identify the model(s) to which the information relates:
ItemSymbolValueUnitItemSymbolValueUnit
Cooling capacity (sensible) Prated,c x,xkWTotal electric power input Pelec x,xxxkW
Cooling capacity (latent) Prated,c x,xkWSound power level (per speed setting, if applicable) LWA x,x/etc.dB
Heating capacity Prated,h x,xkW
Contact detailsName and address of the manufacturer or of its authorised representative.
Table 14
Information requirements for heat pumps

If Cdh is not determined by measurement then the default degradation coefficient of heat pumps shall be 0,25.

From 26 September 2018.

(*)

Where information relates to multi-split heat pumps, the test result and performance data may be obtained on the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.

Information to identify the model(s) to which the information relates:
Outdoor side heat exchanger of heat pump: [select which: air/water/brine]
Indoor side heat exchanger of heat pump: [select which: air/water/brine]
Indication if the heater is equipped with a supplementary heater: yes/no
If applicable: driver of compressor: [electric motor or fuel driven, gaseous or liquid fuel, internal or external combustion engine]
Parameters shall be declared for the average heating season, parameters for the warmer and colder heating seasons are optional.
ItemSymbolValueUnitItemSymbolValueUnit
Rated heating capacity Prated,h x,xkWSeasonal space heating energy efficiency ηs,h x,x%
Declared heating capacity for part load at indoor temperature 20 °C and outdoor temperature Tj Declared coefficient of performance or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Tj = – 7 °C Pdh x,xkW Tj = – 7 °C COPd or GUEh,bin/AEFh,bin x,x%
Tj = + 2 °C Pdh x,xkW Tj = + 2 °C COPd or GUEh,bin/AEFh,bin x,x%
Tj = + 7 °C Pdh x,xkW T j = + 7 °C COPd or GUEh,bin/AEFh,bin x,x%
Tj = + 12 °C Pdh x,xkW Tj = + 12 °C COPd or GUEh,bin/AEFh,bin x,x%
Tbiv = bivalent temperature Pdh x,xkW Tbiv = bivalent temperature COPd or GUEh,bin/AEFh,bin x,x%
TOL = operation limit Pdh x,xkW TOL = operation limit COPd or GUEh,bin/AEFh,bin x,x%
For air-to-water heat pumps: Tj = – 15 °C (if TOL < – 20 °C) Pdh x,xkWFor water-to-air heat pumps: Tj = – 15 °C (if TOL < – 20 °C) COPd or GUEh,bin/AEFh,bin x,x%
Bivalent temperature Tbiv x°CFor water-to-air heat pumps: Operation limit temperature Tol x°C
Degradation co-efficient heat pumpsf9 Cdh x,x—
Power consumption in modes other than ‘active mode’Supplementary heater
Off mode POFF x,xxxkWBack-up heating capacity (*)elbux,xkW
Thermostat-off mode PTO x,xxxkWType of energy input
Crankcase heater mode PCK x,xxxkWStandby mode PSB x,xxxkW
Other items
Capacity controlfixed/staged/variableFor air-to-air heat pumps: air flow rate, outdoor measured—xm3/h
Sound power level, indoor/outdoor measured LWA x,x/x,xdBFor water/brine-to-air heat pumps: Rated brine or water flow rate, outdoor side heat exchanger—xm3/h
Emissions of nitrogen oxides (if applicable)NOx f10 xmg/kWh fuel input GCV
GWP of the refrigerantkg CO2 eq (100 years)
Contact detailsName and address of the manufacturer or of its authorised representative.
Table 15
Information requirements for high temperature process chillers

If Cdc is not determined by measurement then the default degradation coefficient chillers shall be 0,9.

For staged capacity units, two values divided by a slash (‘/’) will be declared in each box in the section referring to ‘refrigeration capacity’ and ‘EER’

Information to identify the model(s) to which the information relates:
Type of condensing: [air-cooled/water-cooled]
Refrigerant fluid(s): [information identifying the refrigerant fluid(s) intended to be used with the process chiller]
ItemSymbolValueUnit
Operating temperature t 7°C
Seasonal energy performance ratio SEPR x,xx[-]
Annual electricity consumption Q xkWh/a
Parameters at full load and reference ambient temperature at rating point Af11
Rated refrigeration capacity PA x,xxkW
Rated power input DA x,xxkW
Rated energy efficiency ratio EERDC,A x,xx[-]
Parameters at rating point B
Declared refrigeration capacity PB x,xxkW
Declared power input DB x,xxkW
Declared energy efficiency ratio EERDC,B x,xx[-]
Parameters at rating point C
Declared refrigeration capacity PC x,xxkW
Declared power input DC x,xxkW
Declared energy efficiency ratio EERDC,C x,xx[-]
Parameters at rating point D
Declared refrigeration capacity PD x,xxkW
Declared power input DD x,xxkW
Declared energy efficiency ratio EERDC,D x,xx[-]
Other items
Capacity controlfixed/staged/variable
Degradation co-efficient chillersf12 Cdc x,xx[-]
GWP of the refrigerantkg CO2 eq (100 years)
Contact detailsName and address of the manufacturer or of its authorised representative.

Annotations

Footnotes

f1

Not required for electric warm air heaters.

f2

From 26 September 2018.

f3

If Cdc is not determined by measurement then the default degradation coefficient of chillers shall be 0,9.

f4

From 26 September 2018.

f5

If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.

f6

From 26 September 2018.

f7

If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.

f8

From 26 September 2018. Where information relates to multi-split air conditioners, the test result and performance data may be obtained on the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.

f9

If Cdh is not determined by measurement then the default degradation coefficient of heat pumps shall be 0,25.

f10

From 26 September 2018.

f11

For staged capacity units, two values divided by a slash (‘/’) will be declared in each box in the section referring to ‘refrigeration capacity’ and ‘EER’

f12

If Cdc is not determined by measurement then the default degradation coefficient chillers shall be 0,9.