Division 5 Product information:
United Kingdom
- (a)
From 1 January 2018, the instruction manuals for installers and end-users, and free access websites of manufacturers, their authorised representatives and importers shall provide the following product information:
- (1)
for warm air heaters, the information set out in Table 9 of this Annex, measured and calculated in accordance with Annex III;
- (2)
for comfort chillers, the information set out in Table 10 of this Annex, measured and calculated in accordance with Annex III;
- (3)
for air-to-air air conditioners, the information set out in Table 11 of this Annex, measured and calculated in accordance with Annex III;
- (4)
for water/brine-to-air air conditioners, the information set out in Table 12 of this Annex, measured and calculated in accordance with Annex III;
- (5)
for fan coil units, the information set out in Table 13 of this Annex, measured and calculated in accordance with Annex III;
- (6)
for heat pumps, the information set out in Table 14 of this Annex, measured and calculated in accordance with Annex III;
- (7)
for high temperature process chillers, the information set out in Table 15 of this Annex, measured and calculated in accordance with Annex III;
- (8)
any specific precautions that must be taken when the product is assembled, installed or maintained;
- (9)
for heat generators or cold generators designed for air heating or cooling products, and air heating or cooling product housings to be equipped with such heat or cold generators, their characteristics, the requirements for assembly, to ensure compliance with the ecodesign requirements for air heating or cooling products and, where appropriate, the list of combinations recommended by the manufacturer;
- (10)
for multi-split heat pumps and multi-split air conditioners, a list of appropriate indoor units;
- (11)
for B1, C2 and C4 warm air heaters the following standard text: ‘This warm air heater is intended to be connected only to a flue shared between multiple dwellings in existing buildings. Due to a lower efficiency, any other use of this warm air heater shall be avoided and would result in higher energy consumption and higher operating costs’.
- (1)
- (b)
From 1 January 2018, the instruction manuals for installers and end-users, and a part for professionals of the free-access websites of manufacturers, their authorised representatives and importers shall provide the following product information:
- (1)
information relevant for disassembly, recycling and/or disposal at end-of-life.
- (1)
- (c)
The technical documentation for the purposes of conformity assessment pursuant to Article 4 shall contain the following elements:
- (1)
the elements specified in point (a);
- (2)
where the information relating to a specific model has been obtained by calculation on the basis of design, and/or extrapolation from other combinations, the technical documentation shall include details of such calculations and/or extrapolations, and of tests undertaken to verify the accuracy of the calculations undertaken, including details of the mathematical model for calculating performance of such combinations, and of measurements taken to verify this model, and a list of any other models where the information included in the technical documentation was obtained on the same basis.
- (1)
- (d)
The manufacturer, their authorised representatives and importers of comfort chillers, air-to-air and water/brine-to-air air conditioners, heat pumps and high temperature process chillers shall provide laboratories performing market surveillance checks, upon request, the necessary information on the setting of the unit, as applied for the establishment of declared capacities, SEER/EER, SCOP/COP, SEPR/COP values, where applicable, and provide contact information for obtaining such information.
| Table 9 | ||||||||
| Information requirements for warm air heaters | ||||||||
| Not required for electric warm air heaters. | ||||||||
| From 26 September 2018. | ||||||||
| Model(s): Information to identify the model(s) to which the information relates: | ||||||||
| B1 warm air heater: [yes/no] | ||||||||
| C2 warm air heater: [yes/no] | ||||||||
| C4 warm air heater: [yes/no] | ||||||||
| Type of fuel: [gas/liquid/electricity] | ||||||||
| Item | Symbol | Value | Unit | Item | Symbol | Value | Unit | |
|---|---|---|---|---|---|---|---|---|
| Capacity | Useful efficiency | |||||||
| Rated heating capacity | Pated,h | x,x | kW | Useful efficiency at rated heating capacityf1 | ηnom | x,x | % | |
| Minimum capacity | Pmin | x,x | kW | Useful efficiency at minimum capacity | ηpl | x,x | % | |
| Electric power consumption | Other items | |||||||
| At rated heating capacity | elmax | x,xxx | kW | Envelope loss factor | Fenv | x,x | % | |
| At minimal capacity | elmin | x,xxx | kW | Ignition burner power consumption | Pign | x,x | kW | |
| In standby mode | elsb | x,xxx | kW | Emissions of nitrogen oxides f2 | NOx | x | mg/kWh input energy (GCV) | |
| Emission efficiency | ηs,flow | x,x | % | |||||
| Seasonal space heating energy efficiency | ηs,h | x,x | % | |||||
| Contact details | Name and address of the manufacturer or of its authorised representative. | |||||||
| Table 10 | ||||||||
| Information requirements for comfort chillers | ||||||||
| If Cdc is not determined by measurement then the default degradation coefficient of chillers shall be 0,9. | ||||||||
| From 26 September 2018. | ||||||||
| Model(s): Information to identify the model(s) to which the information relates: | ||||||||
| Outdoor side heat exchanger of chiller: [select which: air or water/brine] | ||||||||
| Indoor side heat exchanger chiller: [default: water] | ||||||||
| Type: compressor driven vapour compression or sorption process | ||||||||
| If applicable: driver of compressor: [electric motor or fuel driven, gaseous or liquid fuel, internal or external combustion engine] | ||||||||
| Item | Symbol | Value | Unit | Item | Symbol | Value | Unit | |
|---|---|---|---|---|---|---|---|---|
| Rated cooling capacity | Prated,c | x,x | kW | Seasonal space cooling energy efficiency | ηs,c | x,x | % | |
| Declared cooling capacity for part load at given outdoor temperatures Tj | Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj | |||||||
| Tj = + 35 °C | Pdc | x,x | kW | Tj = + 35 °C | EERd or GUEc,bin/AEFc,bin | x,x | % | |
| Tj = + 30 °C | Pdc | x,x | kW | Tj = + 30 °C | EERd or GUEc,bin/AEFc,bin | x,x | % | |
| Tj = + 25 °C | Pdc | x,x | kW | Tj = + 25 °C | EERd or GUEc,bin/AEFc,bin | x,x | % | |
| Tj = + 20 °C | Pdc | x,x | kW | Tj = + 20 °C | EERd or GUEc,bin/AEFc,bin | x,x | % | |
| Degradation co-efficient for chillersf3 | Cdc | x,x | — | |||||
| Power consumption in modes other than ‘active mode’ | ||||||||
| Off mode | POFF | x,xxx | kW | Crankcase heater mode | PCK | x,xxx | kW | |
| Thermostat-off mode | PTO | x,xxx | kW | Standby mode | PSB | x,xxx | kW | |
| Other items | ||||||||
| Capacity control | fixed/staged/variable | For air-to-water comfort chillers: air flow rate, outdoor measured | — | x | m3/h | |||
| Sound power level, outdoor | LWA | x,x/x,x | dB | For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side heat exchanger | — | x | m3/h | |
| Emissions of nitrogen oxides (if applicable) | NOx f4 | x | mg/kWh input GCV | |||||
| GWP of the refrigerant | kg CO2 eq (100 years) | |||||||
| Standard rating conditions used: [low temperature application/medium temperature application] | ||||||||
| Contact details | Name and address of the manufacturer or of its authorised representative. | |||||||
| Table 11 | ||||||||
| Information requirements for air-to-air air conditioners | ||||||||
| If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25. | ||||||||
| From 26 September 2018. | ||||||||
| Where information relates to multi-split air conditioners, the test result and performance data may be obtained on the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer. | ||||||||
| Model(s): Information to identify the model(s) to which the information relates: | ||||||||
| Outdoor side heat exchanger of air conditioner: [default: air] | ||||||||
| Indoor side heat exchanger of air conditioner: [default: air] | ||||||||
| Type: compressor driven vapour compression or sorption process | ||||||||
| If applicable: driver of compressor: [electric motor or fuel driven, gaseous or liquid fuel, internal or external combustion engine] | ||||||||
| Item | Symbol | Value | Unit | Item | Symbol | Value | Unit | |
|---|---|---|---|---|---|---|---|---|
| Rated cooling capacity | Prated,c | x,x | kW | Seasonal space cooling energy efficiency | ηs,c | x,x | % | |
| Declared cooling capacity for part load at given outdoor temperatures Tj and indoor 27°/19 °C (dry/wet bulb) | Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj | |||||||
| Tj = + 35 °C | Pdc | x,x | kW | Tj = + 35 °C | EERd or GUEc,bin/AEFc,bin | x,x | % | |
| Tj = + 30 °C | Pdc | x,x | kW | Tj = + 30 °C | EERd or GUEc,bin/AEFc,bin | x,x | % | |
| Tj = + 25 °C | Pdc | x,x | kW | Tj = + 25 °C | EERd or GUEc,bin/AEFc,bin | x,x | % | |
| Tj = + 20 °C | Pdc | x,x | kW | Tj = + 20 °C | EERd or GUEc,bin/AEFc,bin | x,x | % | |
| Degradation co-efficient for air conditionersf5 | Cdc | x,x | — | |||||
| Power consumption in modes other than ‘active mode’ | ||||||||
| Off mode | POFF | x,xxx | kW | Crankcase heater mode | PCK | x,xxx | kW | |
| Thermostat-off mode | PTO | x,xxx | kW | Standby mode | PSB | x,xxx | kW | |
| Other items | ||||||||
| Capacity control | fixed/staged/variable | For air-to-air air conditioner: air flow rate, outdoor measured | — | x | m3/h | |||
| Sound power level, outdoor | LWA | x,x/x,x | dB | |||||
| If engine driven: Emissions of nitrogen oxides | NOx f6 | x | mg/kWh fuel input GCV | |||||
| GWP of the refrigerant | kg CO2 eq (100 years) | |||||||
| Contact details | Name and address of the manufacturer or of its authorised representative. | |||||||
| Table 12 | ||||||||||
| Information requirements for water/brine-to-air air conditioners | ||||||||||
| If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25. | ||||||||||
| From 26 September 2018. Where information relates to multi-split air conditioners, the test result and performance data may be obtained on the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer. | ||||||||||
| Model(s): Information to identify the model(s) to which the information relates: | ||||||||||
| Outdoor side heat exchanger of air conditioner: [default: water/brine] | ||||||||||
| Indoor side heat exchanger of air conditioner: [default: air] | ||||||||||
| Type: compressor driven vapour compression or sorption process | ||||||||||
| If applicable: driver of compressor: [electric motor or fuel driven, gaseous or liquid fuel, internal or external combustion engine] | ||||||||||
| Item | Symbol | Value | Unit | Item | Symbol | Value | Unit | |||
|---|---|---|---|---|---|---|---|---|---|---|
| Rated cooling capacity | Prated,c | x,x | kW | Seasonal space cooling energy efficiency | ηs,c | x,x | % | |||
| Declared cooling capacity for part load at given outdoor temperatures Tj and indoor 27°/19 °C (dry/wet bulb) | Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj | |||||||||
| Outdoor temperature Tj | cooling tower (inlet/outlet) | ground coupled | ||||||||
| Tj = + 35 °C | 30/35 | 10/15 | Pdc | x,x | kW | Tj = + 35 °C | EERd or GUEc,bin/AEFc,bin | x,x | % | |
| Tj = + 30 °C | 26/* | 10/* | Pdc | x,x | kW | Tj = + 30 °C | EERd or GUEc,bin/AEFc,bin | x,x | % | |
| Tj = + 25 °C | 22/* | 10/* | Pdc | x,x | kW | Tj = + 25 °C | EERd or GUEc,bin/AEFc,bin | x,x | % | |
| Tj = + 20 °C | 18/* | 10/* | Pdc | x,x | kW | Tj = + 20 °C | EERd or GUEc,bin/AEFc,bin | x,x | % | |
| Degradation co-efficient for air conditionersf7 | Cdc | x,x | — | |||||||
| Power consumption in modes other than ‘active mode’ | ||||||||||
| Off mode | POFF | x,xxx | kW | Crankcase heater mode | PCK | x,xxx | kW | |||
| Thermostat-off mode | PTO | x,xxx | kW | Standby mode | PSB | x,xxx | kW | |||
| Other items | ||||||||||
| Capacity control | fixed/staged/variable | |||||||||
| Sound power level, outdoor | LWA | x,x/x,x | dB | For water/brine-to-air air conditioners: Rated brine or water flow rate, outdoor side heat exchanger | — | x | m3/h | |||
| If engine driven Emissions of nitrogen oxides (if applicable) | NOx f8 | x | mg/kWh fuel input GCV | |||||||
| GWP of the refrigerant | kg CO2 eq (100 years) | |||||||||
| Contact details | Name and address of the manufacturer or of its authorised representative. | |||||||||
| Table 13 | ||||||||
| Information requirements for fan coil units | ||||||||
| Information to identify the model(s) to which the information relates: | ||||||||
| Item | Symbol | Value | Unit | Item | Symbol | Value | Unit | |
|---|---|---|---|---|---|---|---|---|
| Cooling capacity (sensible) | Prated,c | x,x | kW | Total electric power input | Pelec | x,xxx | kW | |
| Cooling capacity (latent) | Prated,c | x,x | kW | Sound power level (per speed setting, if applicable) | LWA | x,x/etc. | dB | |
| Heating capacity | Prated,h | x,x | kW | |||||
| Contact details | Name and address of the manufacturer or of its authorised representative. | |||||||
| Table 14 | ||||||||
| Information requirements for heat pumps | ||||||||
| If Cdh is not determined by measurement then the default degradation coefficient of heat pumps shall be 0,25. | ||||||||
| From 26 September 2018. | ||||||||
| (*) | ||||||||
| Where information relates to multi-split heat pumps, the test result and performance data may be obtained on the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer. | ||||||||
| Information to identify the model(s) to which the information relates: | ||||||||
| Outdoor side heat exchanger of heat pump: [select which: air/water/brine] | ||||||||
| Indoor side heat exchanger of heat pump: [select which: air/water/brine] | ||||||||
| Indication if the heater is equipped with a supplementary heater: yes/no | ||||||||
| If applicable: driver of compressor: [electric motor or fuel driven, gaseous or liquid fuel, internal or external combustion engine] | ||||||||
| Parameters shall be declared for the average heating season, parameters for the warmer and colder heating seasons are optional. | ||||||||
| Item | Symbol | Value | Unit | Item | Symbol | Value | Unit | |
|---|---|---|---|---|---|---|---|---|
| Rated heating capacity | Prated,h | x,x | kW | Seasonal space heating energy efficiency | ηs,h | x,x | % | |
| Declared heating capacity for part load at indoor temperature 20 °C and outdoor temperature Tj | Declared coefficient of performance or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj | |||||||
| Tj = – 7 °C | Pdh | x,x | kW | Tj = – 7 °C | COPd or GUEh,bin/AEFh,bin | x,x | % | |
| Tj = + 2 °C | Pdh | x,x | kW | Tj = + 2 °C | COPd or GUEh,bin/AEFh,bin | x,x | % | |
| Tj = + 7 °C | Pdh | x,x | kW | T j = + 7 °C | COPd or GUEh,bin/AEFh,bin | x,x | % | |
| Tj = + 12 °C | Pdh | x,x | kW | Tj = + 12 °C | COPd or GUEh,bin/AEFh,bin | x,x | % | |
| Tbiv = bivalent temperature | Pdh | x,x | kW | Tbiv = bivalent temperature | COPd or GUEh,bin/AEFh,bin | x,x | % | |
| TOL = operation limit | Pdh | x,x | kW | TOL = operation limit | COPd or GUEh,bin/AEFh,bin | x,x | % | |
| For air-to-water heat pumps: Tj = – 15 °C (if TOL < – 20 °C) | Pdh | x,x | kW | For water-to-air heat pumps: Tj = – 15 °C (if TOL < – 20 °C) | COPd or GUEh,bin/AEFh,bin | x,x | % | |
| Bivalent temperature | Tbiv | x | °C | For water-to-air heat pumps: Operation limit temperature | Tol | x | °C | |
| Degradation co-efficient heat pumpsf9 | Cdh | x,x | — | |||||
| Power consumption in modes other than ‘active mode’ | Supplementary heater | |||||||
| Off mode | POFF | x,xxx | kW | Back-up heating capacity (*) | elbu | x,x | kW | |
| Thermostat-off mode | PTO | x,xxx | kW | Type of energy input | ||||
| Crankcase heater mode | PCK | x,xxx | kW | Standby mode | PSB | x,xxx | kW | |
| Other items | ||||||||
| Capacity control | fixed/staged/variable | For air-to-air heat pumps: air flow rate, outdoor measured | — | x | m3/h | |||
| Sound power level, indoor/outdoor measured | LWA | x,x/x,x | dB | For water/brine-to-air heat pumps: Rated brine or water flow rate, outdoor side heat exchanger | — | x | m3/h | |
| Emissions of nitrogen oxides (if applicable) | NOx f10 | x | mg/kWh fuel input GCV | |||||
| GWP of the refrigerant | kg CO2 eq (100 years) | |||||||
| Contact details | Name and address of the manufacturer or of its authorised representative. | |||||||
| Table 15 | ||||
| Information requirements for high temperature process chillers | ||||
| If Cdc is not determined by measurement then the default degradation coefficient chillers shall be 0,9. | ||||
| For staged capacity units, two values divided by a slash (‘/’) will be declared in each box in the section referring to ‘refrigeration capacity’ and ‘EER’ | ||||
| Information to identify the model(s) to which the information relates: | ||||
| Type of condensing: [air-cooled/water-cooled] | ||||
| Refrigerant fluid(s): [information identifying the refrigerant fluid(s) intended to be used with the process chiller] | ||||
| Item | Symbol | Value | Unit | |
|---|---|---|---|---|
| Operating temperature | t | 7 | °C | |
| Seasonal energy performance ratio | SEPR | x,xx | [-] | |
| Annual electricity consumption | Q | x | kWh/a | |
| Parameters at full load and reference ambient temperature at rating point Af11 | ||||
| Rated refrigeration capacity | PA | x,xx | kW | |
| Rated power input | DA | x,xx | kW | |
| Rated energy efficiency ratio | EERDC,A | x,xx | [-] | |
| Parameters at rating point B | ||||
| Declared refrigeration capacity | PB | x,xx | kW | |
| Declared power input | DB | x,xx | kW | |
| Declared energy efficiency ratio | EERDC,B | x,xx | [-] | |
| Parameters at rating point C | ||||
| Declared refrigeration capacity | PC | x,xx | kW | |
| Declared power input | DC | x,xx | kW | |
| Declared energy efficiency ratio | EERDC,C | x,xx | [-] | |
| Parameters at rating point D | ||||
| Declared refrigeration capacity | PD | x,xx | kW | |
| Declared power input | DD | x,xx | kW | |
| Declared energy efficiency ratio | EERDC,D | x,xx | [-] | |
| Other items | ||||
| Capacity control | fixed/staged/variable | |||
| Degradation co-efficient chillersf12 | Cdc | x,xx | [-] | |
| GWP of the refrigerant | kg CO2 eq (100 years) | |||
| Contact details | Name and address of the manufacturer or of its authorised representative. | |||
Annotations
Footnotes
- f1
-
Not required for electric warm air heaters.
- f2
-
From 26 September 2018.
- f3
-
If Cdc is not determined by measurement then the default degradation coefficient of chillers shall be 0,9.
- f4
-
From 26 September 2018.
- f5
-
If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
- f6
-
From 26 September 2018.
- f7
-
If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
- f8
-
From 26 September 2018. Where information relates to multi-split air conditioners, the test result and performance data may be obtained on the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
- f9
-
If Cdh is not determined by measurement then the default degradation coefficient of heat pumps shall be 0,25.
- f10
-
From 26 September 2018.
- f11
-
For staged capacity units, two values divided by a slash (‘/’) will be declared in each box in the section referring to ‘refrigeration capacity’ and ‘EER’
- f12
-
If Cdc is not determined by measurement then the default degradation coefficient chillers shall be 0,9.