For establishing the values of rated and declared cooling capacity, power input, energy efficiency ratio and the seasonal energy performance ratio, measurements shall be done using the following conditions:

  1. (a)

    the reference ambient temperature at the outdoor side heat exchanger shall be 35 °C for air-cooled high temperature process chillers and 30 °C water inlet temperature to the condenser (rating point with 35 °C outdoor air temperature) for water-cooled high temperature process chillers

  2. (b)

    the outlet temperature of the liquid at the indoor side heat exchanger shall be 7 °C dry bulb temperature;

  3. (c)

    the variations of the ambient temperature throughout the year, representative of average climate conditions in the European Union, and the corresponding number of hours when these temperatures occur, shall be as set out in Table 28;

  4. (d)

    the effect of the degradation of energy efficiency caused by cycling depending on the type of capacity control of the high temperature process chiller shall be measured or a default value shall be used.

Table 16

Standard rating conditions for air-to-air heat pumps and air conditioners

The wet bulb temperature condition is not required when testing units which do not evaporate condensate.

Outdoor side heat exchangerIndoor side heat exchanger
inlet dry bulb temperature °Cinlet wet bulb temperature °Cinlet dry bulb temperature °Cinlet wet bulb temperature °C
Heating mode (for heat pumps)Outside air/recycled air762015 max
Exhaust air/outdoor air201276
Cooling mode (for air conditioners)Outside air/recycled air3524f1 2719
Exhaust air/recycled air27192719
Exhaust air/outdoor air27193524

Table 17

Standard rating conditions for water/brine-to-water comfort chillers

Outdoor side heat exchangerIndoor side heat exchanger
inlet temperature °Coutlet temperature °Cinlet temperature °Coutlet temperature °C
Cooling modewater-to-water (for low temperature heating applications) from cooling tower3035127
water-to-water (for medium temperature heating applications) from cooling tower30352318

Table 18

Standard rating conditions air-to-water comfort chillers

Outdoor side heat exchangerIndoor side heat exchanger
inlet temperature °Coutlet temperature °Cinlet temperature °Coutlet temperature °C
Cooling modeair-to-water (for low temperature applications)35—127
air-to-water (for medium temperature applications)35—2318

Table 19

Standard rating conditions for water/brine-to-air heat pumps and air conditioners

For units designed for heating and cooling mode, the flow rate obtained during the test at standard rating conditions in cooling mode is used.

Outdoor side heat exchangerIndoor side heat exchanger
inlet temperature °Coutlet temperature °Cinlet dry bulb temperature °Cinlet wet bulb temperature °C
Heating mode (for heat pumps)water1072015 max
brine0– 3f2 2015 max
water loop2017 2015 max
Cooling mode (for air conditioners)cooling tower30352719
ground coupled (water or brine)10152719

Table 20

Reference ambient temperatures for high temperature process chillers

Test pointPart load ratio of high temperature process chillersPart load ratio (%)Outdoor side heat exchanger (°C)Indoor side heat exchanger
Evaporator inlet/outlet water temperatures (°C)
Fixed outlet
A80 % + 20 % × (TA -TD )/(TA -TD )100

Inlet air temperature

35

12/7

Inlet/outlet water temperatures

30/35

Table 21

Part load conditions for air conditioners, comfort chillers and heat pumps

Outlet temperatures dependent on water flow rate as determined at standard rating conditions (100 % part load ratio when cooling, 88 % when heating)

Rating pointOutdoor temperaturePart load ratioOutdoor side heat exchangerIndoor side heat exchanger
Air-to-air air conditioners
Tj (°C)Outdoor air dry bulb temperatures (°C)Indoor air dry bulb (wet bulb) temperatures (°C)
A35100 %3527 (19)
B3074 %3027 (19)
C2547 %2527 (19)
D2021 %2027 (19)
Water-to-air air conditioners
Rating point Tj (°C)Part load ratioCooling tower or water loop application inlet/outlet temperatures (°C)Ground coupled application (water or brine) inlet/outlet temperatures (°C)Indoor air dry bulb (wet bulb) temperatures (°C)
A35100 %30/3510/1527 (19)
B3074 %26/f3 10/ 27 (19)
C2547 %22/ 10/ 27 (19)
D2021 %18/ 10/ 27 (19)
Air-to-water comfort chillers
Rating point Tj (°C)Part load ratioOutdoor air dry bulb temperatures (°C)Fan coil application inlet/outlet water temperatures (°C)Cooling floor application inlet/outlet water temperatures (°C)
Fixed outletVariable outlet
A35100 %3512/712/723/18
B3074 %30 /7 /8,5 /18
C2547 %25 /7 /10 /18
D2021 %20 /7 /11,5 /18
Water-to-water comfort chillers
Rating point Tj (°C)Part load ratioCooling tower or water loop application inlet/outlet temperatures (°C)Ground coupled application (water or brine) inlet/outlet temperatures (°C)Fan coil application inlet/outlet water temperatures (°C)Cooling floor application inlet/outlet water temperatures (°C)
Fixed outletVariable outlet
A35100 %30/3510/1512/712/723/18
B3074 %26/ 10/ /7 /8,5 /18
C2547 %22/ 10/ /7 /10 /18
D2021 %18/ 10/ /7 /11,5 /18
Air-to-air heat pumps
Rating point Tj (°C)Part load ratioOutdoor air dry bulb (wet bulb) temperatures (°C)Indoor air dry bulb temperature (°C)
A– 788 %– 7(– 8)20
B+ 254 %+ 2(+ 1)20
C+ 735 %+ 7(+ 6)20
D+ 1215 %+ 12(+ 11)20
ETol depends on Tol Tj = Tol 20
FTbiv depends on Tbiv Tj = Tbiv 20
Water/brine-to-air heat pumps
Rating point Tj (°C)Part load ratioGround WaterBrineIndoor air dry bulb temperature (°C)
Inlet/outlet temperatures (°C)Inlet/outlet temperatures (°C)
A– 788 %10/ 0/ 20
B+ 254 %10/ 0/ 20
C+ 735 %10/ 0/ 20
D+ 1215 %10/ 0/ 20
ETol depends on Tol 10/ 0/ 20
FTbiv depends on Tbiv 10/ 0/ 20

Table 22

Part load conditions for SEPR calculation for air-cooled high temperature process chillers

With the water flow rate determined during ‘A’ test for units with a fixed water flow rate or with a variable flow rate.

Rating pointPart load ratio of high temperature process chillersPart load ratio (%)Outdoor side heat exchangerIndoor side heat exchanger
Inlet air temperature (°C)Evaporator inlet/outlet water temperatures (°C)
Fixed outlet
A80 % + 20 % × (TA -TD )/(TA -TD )1003512/7
B80 % + 20 % × (TB -TD )/(TA -TD )9325 f4/7
C80 % + 20 % × (TC -TD )/(TA -TD )8715 /7
D80 % + 20 % × (TD -TD )/(TA -TD )805 /7

Table 23

Part load conditions for SEPR calculation for water-cooled high temperature process chillers

With the water flow rate determined during ‘A’ test for units with a fixed water flow rate or with a variable flow rate.

Rating pointPart load ratio of high temperature process chillersPart load ratio (%)Water-cooled condenserIndoor side heat exchanger
Inlet/outlet water temperatures (°C)Outdoor air temperature (°C)Evaporator Inlet/outlet water temperatures (°C)
Fixed outlet
A80 % + 20 % × (TA -TD )/(TA -TD )10030/353512/7
B80 % + 20 % × (T B-T D)/(T A-T D)9323/f5 25 /7
C80 % + 20 % × (T C-T D)/(T A-T D)8716/ 15 /7
D80 % + 20 % × (TD-TD)/(TA-TD)809/ 5 /7

Table 24

Reference design conditions for comfort chillers, air conditioners and heat pumps

FunctionSeasonReference design temperature dry bulb (wet bulb)
Tdesign,c
CoolingAverage35 (24) °C
Reference design temperatureBivalent temperature maximumOperation limit temperature maximum
Tdesign,h Tbiv Tol
HeatingAverage– 10 (– 11) °C+ 2 °C– 7 °C
Warmer2 (– 1) °C7 °C2 °C
Colder– 22 (– 23) °C– 7 °C– 15 °C

Table 25

Standard rating conditions for fan coil units

Cooling testHeating testSound power test
Air temperature

27 °C (dry bulb)

19 °C (wet bulb)

Air temperature20 °C (dry bulb)At ambient conditions without water flow
Inlet water temperature7 °CInlet water temperature

45 °C for 2-pipe units

65 °C for 4-pipe units

Water temperature rise5 °CWater temperature decrease

5 °C for 2-pipe units

10 °C for 4-pipe units

Table 26

European heating seasons for heat pumps

binj Tj (°C) Hj (h/annum)
WarmerAverageColder
1 to 8– 30 to – 23000
9– 22001
10– 21006
11– 200013
12– 190017
13– 180019
14– 170026
15– 160039
16– 150041
17– 140035
18– 130052
19– 120037
20– 110041
21– 100143
22– 902554
23– 802390
24– 7024125
25– 6027169
26– 5068195
27– 4091278
28– 3089306
29– 20165454
30– 10173385
3100240490
3210280533
3323320380
34322357228
35463356261
36563303279
376175330229
387162326269
398259348233
409360335230
4110428315243
4211430215191
4312503169146
4413444151150
451438410597
46152947461
Total hours:3 5904 9106 446

Table 27

European cooling season for comfort chillers and air conditioners

BinsOutdoor temperature (dry bulb)‘Average cooling season’ EER calculation
bin hours
jTj hj
#°Ch/annum
117205EER(D)
218227EER(D)
319225EER(D)
420225D — Measured value
521216Linear interpolation
622215Linear interpolation
723218Linear interpolation
824197Linear interpolation
925178C — Measured value
1026158Linear interpolation
1127137Linear interpolation
1228109Linear interpolation
132988Linear interpolation
143063B — Measured value
153139Linear interpolation
163231Linear interpolation
173324Linear interpolation
183417Linear interpolation
193513A — Measured value
20369EER(A)
21374EER(A)
22383EER(A)
23391EER(A)
24400EER(A)

Table 28

European reference refrigeration season for high temperature process chillers

binj Tj (°C) Hj (h/annum)
1– 190,08
2– 180,41
3– 170,65
4– 161,05
5– 151,74
6– 142,98
7– 133,79
8– 125,69
9– 118,94
10– 1011,81
11– 917,29
12– 820,02
13– 728,73
14– 639,71
15– 556,61
16– 476,36
17– 3106,07
18– 2153,22
19– 1203,41
200247,98
211282,01
222275,91
233300,61
244310,77
255336,48
266350,48
277363,49
288368,91
299371,63
3010377,32
3111376,53
3212386,42
3313389,84
3414384,45
3515370,45
3616344,96
3717328,02
3818305,36
3919261,87
4020223,90
4121196,31
4222163,04
4323141,78
4424121,93
4525104,46
462685,77
472771,54
482856,57
492943,35
503031,02
513120,21
523211,85
53338,17
54343,83
55352,09
56361,21
57370,52
58380,40

Table 29

Operational hours per functional mode for comfort chillers, air conditioners and heat pumps

SeasonOperational hours
On-modeThermostat Off modeStandby modeOff modeCrankcase heater mode
HCE (cooling); HHE (heating)HTO HSB HOFF HCK
Cooling (to calculate SEER)Average6006591 37702 036
Colder30043682801 264
Warmer9007671 64702 414
Heating only (to calculate SCOP)Average1 40017903 6723 851
Colder2 10013102 1892 320
Warmer1 40075504 3455 100
Heating, if reversible (to calculate SCOP)Average1 40017900179
Colder2 10013100131
Warmer1 40075500755
  1. 1Division 1
  2. 2General conditions for measurements and calculations:
  3. 3Seasonal space heating energy efficiency of warm air heaters:
  4. 4Seasonal space cooling energy efficiency of comfort chillers and air conditioners when driven by electric motors:
  5. 5Seasonal space cooling energy efficiency of comfort chillers and air conditioners using internal combustion engine:
  6. 6Seasonal space heating energy efficiency of electric heat pumps:
  7. 7Seasonal space heating energy efficiency of heat pumps using internal combustion engine:
  8. 8Division 8

Annotations

Footnotes

f1

The wet bulb temperature condition is not required when testing units which do not evaporate condensate.

f2

For units designed for heating and cooling mode, the flow rate obtained during the test at standard rating conditions in cooling mode is used.

f3

Outlet temperatures dependent on water flow rate as determined at standard rating conditions (100 % part load ratio when cooling, 88 % when heating)

f4

With the water flow rate determined during ‘A’ test for units with a fixed water flow rate or with a variable flow rate.

f5

With the water flow rate determined during ‘A’ test for units with a fixed water flow rate or with a variable flow rate.