Annex III Measurement and calculation
United Kingdom
For establishing the values of rated and declared cooling capacity, power input, energy efficiency ratio and the seasonal energy performance ratio, measurements shall be done using the following conditions:
- (a)
the reference ambient temperature at the outdoor side heat exchanger shall be 35 °C for air-cooled high temperature process chillers and 30 °C water inlet temperature to the condenser (rating point with 35 °C outdoor air temperature) for water-cooled high temperature process chillers
- (b)
the outlet temperature of the liquid at the indoor side heat exchanger shall be 7 °C dry bulb temperature;
- (c)
the variations of the ambient temperature throughout the year, representative of average climate conditions in the European Union, and the corresponding number of hours when these temperatures occur, shall be as set out in Table 28;
- (d)
the effect of the degradation of energy efficiency caused by cycling depending on the type of capacity control of the high temperature process chiller shall be measured or a default value shall be used.
Table 16
Standard rating conditions for air-to-air heat pumps and air conditioners
The wet bulb temperature condition is not required when testing units which do not evaporate condensate. | |||||
| Outdoor side heat exchanger | Indoor side heat exchanger | ||||
|---|---|---|---|---|---|
| inlet dry bulb temperature °C | inlet wet bulb temperature °C | inlet dry bulb temperature °C | inlet wet bulb temperature °C | ||
| Heating mode (for heat pumps) | Outside air/recycled air | 7 | 6 | 20 | 15 max |
| Exhaust air/outdoor air | 20 | 12 | 7 | 6 | |
| Cooling mode (for air conditioners) | Outside air/recycled air | 35 | 24f1 | 27 | 19 |
| Exhaust air/recycled air | 27 | 19 | 27 | 19 | |
| Exhaust air/outdoor air | 27 | 19 | 35 | 24 | |
Table 17
Standard rating conditions for water/brine-to-water comfort chillers
| Outdoor side heat exchanger | Indoor side heat exchanger | ||||
|---|---|---|---|---|---|
| inlet temperature °C | outlet temperature °C | inlet temperature °C | outlet temperature °C | ||
| Cooling mode | water-to-water (for low temperature heating applications) from cooling tower | 30 | 35 | 12 | 7 |
| water-to-water (for medium temperature heating applications) from cooling tower | 30 | 35 | 23 | 18 | |
Table 18
Standard rating conditions air-to-water comfort chillers
| Outdoor side heat exchanger | Indoor side heat exchanger | ||||
|---|---|---|---|---|---|
| inlet temperature °C | outlet temperature °C | inlet temperature °C | outlet temperature °C | ||
| Cooling mode | air-to-water (for low temperature applications) | 35 | — | 12 | 7 |
| air-to-water (for medium temperature applications) | 35 | — | 23 | 18 | |
Table 19
Standard rating conditions for water/brine-to-air heat pumps and air conditioners
For units designed for heating and cooling mode, the flow rate obtained during the test at standard rating conditions in cooling mode is used. | |||||
| Outdoor side heat exchanger | Indoor side heat exchanger | ||||
|---|---|---|---|---|---|
| inlet temperature °C | outlet temperature °C | inlet dry bulb temperature °C | inlet wet bulb temperature °C | ||
| Heating mode (for heat pumps) | water | 10 | 7 | 20 | 15 max |
| brine | 0 | – 3f2 | 20 | 15 max | |
| water loop | 20 | 17 | 20 | 15 max | |
| Cooling mode (for air conditioners) | cooling tower | 30 | 35 | 27 | 19 |
| ground coupled (water or brine) | 10 | 15 | 27 | 19 | |
Table 20
Reference ambient temperatures for high temperature process chillers
| Test point | Part load ratio of high temperature process chillers | Part load ratio (%) | Outdoor side heat exchanger (°C) | Indoor side heat exchanger |
|---|---|---|---|---|
| Evaporator inlet/outlet water temperatures (°C) | ||||
| Fixed outlet | ||||
| A | 80 % + 20 % × (TA -TD )/(TA -TD ) | 100 | Inlet air temperature 35 | 12/7 |
Inlet/outlet water temperatures 30/35 |
Table 21
Part load conditions for air conditioners, comfort chillers and heat pumps
Outlet temperatures dependent on water flow rate as determined at standard rating conditions (100 % part load ratio when cooling, 88 % when heating) | |||||||
| Rating point | Outdoor temperature | Part load ratio | Outdoor side heat exchanger | Indoor side heat exchanger | |||
|---|---|---|---|---|---|---|---|
| Air-to-air air conditioners | |||||||
| Tj (°C) | Outdoor air dry bulb temperatures (°C) | Indoor air dry bulb (wet bulb) temperatures (°C) | |||||
| A | 35 | 100 % | 35 | 27 (19) | |||
| B | 30 | 74 % | 30 | 27 (19) | |||
| C | 25 | 47 % | 25 | 27 (19) | |||
| D | 20 | 21 % | 20 | 27 (19) | |||
| Water-to-air air conditioners | |||||||
| Rating point | Tj (°C) | Part load ratio | Cooling tower or water loop application inlet/outlet temperatures (°C) | Ground coupled application (water or brine) inlet/outlet temperatures (°C) | Indoor air dry bulb (wet bulb) temperatures (°C) | ||
| A | 35 | 100 % | 30/35 | 10/15 | 27 (19) | ||
| B | 30 | 74 % | 26/f3 | 10/ | 27 (19) | ||
| C | 25 | 47 % | 22/ | 10/ | 27 (19) | ||
| D | 20 | 21 % | 18/ | 10/ | 27 (19) | ||
| Air-to-water comfort chillers | |||||||
| Rating point | Tj (°C) | Part load ratio | Outdoor air dry bulb temperatures (°C) | Fan coil application inlet/outlet water temperatures (°C) | Cooling floor application inlet/outlet water temperatures (°C) | ||
| Fixed outlet | Variable outlet | ||||||
| A | 35 | 100 % | 35 | 12/7 | 12/7 | 23/18 | |
| B | 30 | 74 % | 30 | /7 | /8,5 | /18 | |
| C | 25 | 47 % | 25 | /7 | /10 | /18 | |
| D | 20 | 21 % | 20 | /7 | /11,5 | /18 | |
| Water-to-water comfort chillers | |||||||
| Rating point | Tj (°C) | Part load ratio | Cooling tower or water loop application inlet/outlet temperatures (°C) | Ground coupled application (water or brine) inlet/outlet temperatures (°C) | Fan coil application inlet/outlet water temperatures (°C) | Cooling floor application inlet/outlet water temperatures (°C) | |
| Fixed outlet | Variable outlet | ||||||
| A | 35 | 100 % | 30/35 | 10/15 | 12/7 | 12/7 | 23/18 |
| B | 30 | 74 % | 26/ | 10/ | /7 | /8,5 | /18 |
| C | 25 | 47 % | 22/ | 10/ | /7 | /10 | /18 |
| D | 20 | 21 % | 18/ | 10/ | /7 | /11,5 | /18 |
| Air-to-air heat pumps | |||||||
| Rating point | Tj (°C) | Part load ratio | Outdoor air dry bulb (wet bulb) temperatures (°C) | Indoor air dry bulb temperature (°C) | |||
| A | – 7 | 88 % | – 7(– 8) | 20 | |||
| B | + 2 | 54 % | + 2(+ 1) | 20 | |||
| C | + 7 | 35 % | + 7(+ 6) | 20 | |||
| D | + 12 | 15 % | + 12(+ 11) | 20 | |||
| E | Tol | depends on Tol | Tj = Tol | 20 | |||
| F | Tbiv | depends on Tbiv | Tj = Tbiv | 20 | |||
| Water/brine-to-air heat pumps | |||||||
| Rating point | Tj (°C) | Part load ratio | Ground Water | Brine | Indoor air dry bulb temperature (°C) | ||
| Inlet/outlet temperatures (°C) | Inlet/outlet temperatures (°C) | ||||||
| A | – 7 | 88 % | 10/ | 0/ | 20 | ||
| B | + 2 | 54 % | 10/ | 0/ | 20 | ||
| C | + 7 | 35 % | 10/ | 0/ | 20 | ||
| D | + 12 | 15 % | 10/ | 0/ | 20 | ||
| E | Tol | depends on Tol | 10/ | 0/ | 20 | ||
| F | Tbiv | depends on Tbiv | 10/ | 0/ | 20 | ||
Table 22
Part load conditions for SEPR calculation for air-cooled high temperature process chillers
With the water flow rate determined during ‘A’ test for units with a fixed water flow rate or with a variable flow rate. | ||||
| Rating point | Part load ratio of high temperature process chillers | Part load ratio (%) | Outdoor side heat exchanger | Indoor side heat exchanger |
|---|---|---|---|---|
| Inlet air temperature (°C) | Evaporator inlet/outlet water temperatures (°C) | |||
| Fixed outlet | ||||
| A | 80 % + 20 % × (TA -TD )/(TA -TD ) | 100 | 35 | 12/7 |
| B | 80 % + 20 % × (TB -TD )/(TA -TD ) | 93 | 25 | f4/7 |
| C | 80 % + 20 % × (TC -TD )/(TA -TD ) | 87 | 15 | /7 |
| D | 80 % + 20 % × (TD -TD )/(TA -TD ) | 80 | 5 | /7 |
Table 23
Part load conditions for SEPR calculation for water-cooled high temperature process chillers
With the water flow rate determined during ‘A’ test for units with a fixed water flow rate or with a variable flow rate. | |||||
| Rating point | Part load ratio of high temperature process chillers | Part load ratio (%) | Water-cooled condenser | Indoor side heat exchanger | |
|---|---|---|---|---|---|
| Inlet/outlet water temperatures (°C) | Outdoor air temperature (°C) | Evaporator Inlet/outlet water temperatures (°C) | |||
| Fixed outlet | |||||
| A | 80 % + 20 % × (TA -TD )/(TA -TD ) | 100 | 30/35 | 35 | 12/7 |
| B | 80 % + 20 % × (T B-T D)/(T A-T D) | 93 | 23/f5 | 25 | /7 |
| C | 80 % + 20 % × (T C-T D)/(T A-T D) | 87 | 16/ | 15 | /7 |
| D | 80 % + 20 % × (TD-TD)/(TA-TD) | 80 | 9/ | 5 | /7 |
Table 24
Reference design conditions for comfort chillers, air conditioners and heat pumps
| Function | Season | Reference design temperature dry bulb (wet bulb) | ||
|---|---|---|---|---|
| Tdesign,c | ||||
| Cooling | Average | 35 (24) °C | ||
| Reference design temperature | Bivalent temperature maximum | Operation limit temperature maximum | ||
| Tdesign,h | Tbiv | Tol | ||
| Heating | Average | – 10 (– 11) °C | + 2 °C | – 7 °C |
| Warmer | 2 (– 1) °C | 7 °C | 2 °C | |
| Colder | – 22 (– 23) °C | – 7 °C | – 15 °C | |
Table 25
Standard rating conditions for fan coil units
| Cooling test | Heating test | Sound power test | ||
|---|---|---|---|---|
| Air temperature | 27 °C (dry bulb) 19 °C (wet bulb) | Air temperature | 20 °C (dry bulb) | At ambient conditions without water flow |
| Inlet water temperature | 7 °C | Inlet water temperature | 45 °C for 2-pipe units 65 °C for 4-pipe units | |
| Water temperature rise | 5 °C | Water temperature decrease | 5 °C for 2-pipe units 10 °C for 4-pipe units | |
Table 26
European heating seasons for heat pumps
| binj | Tj (°C) | Hj (h/annum) | ||
|---|---|---|---|---|
| Warmer | Average | Colder | ||
| 1 to 8 | – 30 to – 23 | 0 | 0 | 0 |
| 9 | – 22 | 0 | 0 | 1 |
| 10 | – 21 | 0 | 0 | 6 |
| 11 | – 20 | 0 | 0 | 13 |
| 12 | – 19 | 0 | 0 | 17 |
| 13 | – 18 | 0 | 0 | 19 |
| 14 | – 17 | 0 | 0 | 26 |
| 15 | – 16 | 0 | 0 | 39 |
| 16 | – 15 | 0 | 0 | 41 |
| 17 | – 14 | 0 | 0 | 35 |
| 18 | – 13 | 0 | 0 | 52 |
| 19 | – 12 | 0 | 0 | 37 |
| 20 | – 11 | 0 | 0 | 41 |
| 21 | – 10 | 0 | 1 | 43 |
| 22 | – 9 | 0 | 25 | 54 |
| 23 | – 8 | 0 | 23 | 90 |
| 24 | – 7 | 0 | 24 | 125 |
| 25 | – 6 | 0 | 27 | 169 |
| 26 | – 5 | 0 | 68 | 195 |
| 27 | – 4 | 0 | 91 | 278 |
| 28 | – 3 | 0 | 89 | 306 |
| 29 | – 2 | 0 | 165 | 454 |
| 30 | – 1 | 0 | 173 | 385 |
| 31 | 0 | 0 | 240 | 490 |
| 32 | 1 | 0 | 280 | 533 |
| 33 | 2 | 3 | 320 | 380 |
| 34 | 3 | 22 | 357 | 228 |
| 35 | 4 | 63 | 356 | 261 |
| 36 | 5 | 63 | 303 | 279 |
| 37 | 6 | 175 | 330 | 229 |
| 38 | 7 | 162 | 326 | 269 |
| 39 | 8 | 259 | 348 | 233 |
| 40 | 9 | 360 | 335 | 230 |
| 41 | 10 | 428 | 315 | 243 |
| 42 | 11 | 430 | 215 | 191 |
| 43 | 12 | 503 | 169 | 146 |
| 44 | 13 | 444 | 151 | 150 |
| 45 | 14 | 384 | 105 | 97 |
| 46 | 15 | 294 | 74 | 61 |
| Total hours: | 3 590 | 4 910 | 6 446 | |
Table 27
European cooling season for comfort chillers and air conditioners
| Bins | Outdoor temperature (dry bulb) | ‘Average cooling season’ | EER calculation |
|---|---|---|---|
| bin hours | |||
| j | Tj | hj | |
| # | °C | h/annum | |
| 1 | 17 | 205 | EER(D) |
| 2 | 18 | 227 | EER(D) |
| 3 | 19 | 225 | EER(D) |
| 4 | 20 | 225 | D — Measured value |
| 5 | 21 | 216 | Linear interpolation |
| 6 | 22 | 215 | Linear interpolation |
| 7 | 23 | 218 | Linear interpolation |
| 8 | 24 | 197 | Linear interpolation |
| 9 | 25 | 178 | C — Measured value |
| 10 | 26 | 158 | Linear interpolation |
| 11 | 27 | 137 | Linear interpolation |
| 12 | 28 | 109 | Linear interpolation |
| 13 | 29 | 88 | Linear interpolation |
| 14 | 30 | 63 | B — Measured value |
| 15 | 31 | 39 | Linear interpolation |
| 16 | 32 | 31 | Linear interpolation |
| 17 | 33 | 24 | Linear interpolation |
| 18 | 34 | 17 | Linear interpolation |
| 19 | 35 | 13 | A — Measured value |
| 20 | 36 | 9 | EER(A) |
| 21 | 37 | 4 | EER(A) |
| 22 | 38 | 3 | EER(A) |
| 23 | 39 | 1 | EER(A) |
| 24 | 40 | 0 | EER(A) |
Table 28
European reference refrigeration season for high temperature process chillers
| binj | Tj (°C) | Hj (h/annum) |
|---|---|---|
| 1 | – 19 | 0,08 |
| 2 | – 18 | 0,41 |
| 3 | – 17 | 0,65 |
| 4 | – 16 | 1,05 |
| 5 | – 15 | 1,74 |
| 6 | – 14 | 2,98 |
| 7 | – 13 | 3,79 |
| 8 | – 12 | 5,69 |
| 9 | – 11 | 8,94 |
| 10 | – 10 | 11,81 |
| 11 | – 9 | 17,29 |
| 12 | – 8 | 20,02 |
| 13 | – 7 | 28,73 |
| 14 | – 6 | 39,71 |
| 15 | – 5 | 56,61 |
| 16 | – 4 | 76,36 |
| 17 | – 3 | 106,07 |
| 18 | – 2 | 153,22 |
| 19 | – 1 | 203,41 |
| 20 | 0 | 247,98 |
| 21 | 1 | 282,01 |
| 22 | 2 | 275,91 |
| 23 | 3 | 300,61 |
| 24 | 4 | 310,77 |
| 25 | 5 | 336,48 |
| 26 | 6 | 350,48 |
| 27 | 7 | 363,49 |
| 28 | 8 | 368,91 |
| 29 | 9 | 371,63 |
| 30 | 10 | 377,32 |
| 31 | 11 | 376,53 |
| 32 | 12 | 386,42 |
| 33 | 13 | 389,84 |
| 34 | 14 | 384,45 |
| 35 | 15 | 370,45 |
| 36 | 16 | 344,96 |
| 37 | 17 | 328,02 |
| 38 | 18 | 305,36 |
| 39 | 19 | 261,87 |
| 40 | 20 | 223,90 |
| 41 | 21 | 196,31 |
| 42 | 22 | 163,04 |
| 43 | 23 | 141,78 |
| 44 | 24 | 121,93 |
| 45 | 25 | 104,46 |
| 46 | 26 | 85,77 |
| 47 | 27 | 71,54 |
| 48 | 28 | 56,57 |
| 49 | 29 | 43,35 |
| 50 | 30 | 31,02 |
| 51 | 31 | 20,21 |
| 52 | 32 | 11,85 |
| 53 | 33 | 8,17 |
| 54 | 34 | 3,83 |
| 55 | 35 | 2,09 |
| 56 | 36 | 1,21 |
| 57 | 37 | 0,52 |
| 58 | 38 | 0,40 |
Table 29
Operational hours per functional mode for comfort chillers, air conditioners and heat pumps
| Season | Operational hours | |||||
|---|---|---|---|---|---|---|
| On-mode | Thermostat Off mode | Standby mode | Off mode | Crankcase heater mode | ||
| HCE (cooling); HHE (heating) | HTO | HSB | HOFF | HCK | ||
| Cooling (to calculate SEER) | Average | 600 | 659 | 1 377 | 0 | 2 036 |
| Colder | 300 | 436 | 828 | 0 | 1 264 | |
| Warmer | 900 | 767 | 1 647 | 0 | 2 414 | |
| Heating only (to calculate SCOP) | Average | 1 400 | 179 | 0 | 3 672 | 3 851 |
| Colder | 2 100 | 131 | 0 | 2 189 | 2 320 | |
| Warmer | 1 400 | 755 | 0 | 4 345 | 5 100 | |
| Heating, if reversible (to calculate SCOP) | Average | 1 400 | 179 | 0 | 0 | 179 |
| Colder | 2 100 | 131 | 0 | 0 | 131 | |
| Warmer | 1 400 | 755 | 0 | 0 | 755 | |
- 1Division 1
- 2General conditions for measurements and calculations:
- 3Seasonal space heating energy efficiency of warm air heaters:
- 4Seasonal space cooling energy efficiency of comfort chillers and air conditioners when driven by electric motors:
- 5Seasonal space cooling energy efficiency of comfort chillers and air conditioners using internal combustion engine:
- 6Seasonal space heating energy efficiency of electric heat pumps:
- 7Seasonal space heating energy efficiency of heat pumps using internal combustion engine:
- 8Division 8
Annotations
Footnotes
- f1
The wet bulb temperature condition is not required when testing units which do not evaporate condensate.
- f2
For units designed for heating and cooling mode, the flow rate obtained during the test at standard rating conditions in cooling mode is used.
- f3
Outlet temperatures dependent on water flow rate as determined at standard rating conditions (100 % part load ratio when cooling, 88 % when heating)
- f4
With the water flow rate determined during ‘A’ test for units with a fixed water flow rate or with a variable flow rate.
- f5
With the water flow rate determined during ‘A’ test for units with a fixed water flow rate or with a variable flow rate.