Division 6 Seasonal space heating energy efficiency of electric heat pumps:
United Kingdom
- (a)
For the purposes of the measurements of heat pumps the indoor ambient temperature shall be set at 20 °C;
- (b)
While establishing the sound power level, the operating conditions shall be the standard rating conditions set out in Table 16 (air-to-air heat pumps), Table 19 (water/brine-to-air heat pumps);
- (c)
The active mode seasonal coefficient of performance SCOPon shall be calculated on the basis of the part load for heating Ph(Tj), the electric back-up heating capacity elbu(Tj ) (if applicable) and the bin-specific coefficient of performance COPbin (Tj) and weighted by the bin-hours the bin conditions occurs, and shall take into account:
- (1)
the reference design conditions set out in Table 24;
- (2)
the European ‘average’ heating season set out in Table 26;
- (3)
if applicable, the effects of the degradation of the energy efficiency caused by cycling depending on the type of control of the heating capacity;
- (1)
- (d)
The reference annual heating demand QH shall be the design heating load Pdesign,h multiplied by the equivalent active mode hours for heating HHE set out in Table 29;
- (e)
The annual energy consumption for heating QHE shall be calculated as the sum of:
- (1)
the ratio of the reference annual heating demand QH and the active mode seasonal coefficient of performance SCOPon; and
- (2)
the energy consumption for thermostat-off, standby, off and crankcase heater mode during the season;
- (1)
- (f)
The seasonal coefficient of performance SCOP shall be calculated as the ratio of the reference annual heating demand QH and the annual energy consumption for heating QHE ;
- (g)
The seasonal space heating energy efficiency ηs,h shall be calculated as the seasonal coefficient of performance SCOP divided by the conversion coefficient CC, corrected by contributions accounting for temperature control and for water/brine-to-air heat pumps only, the electricity consumption of ground water pump(s);
- (h)
For multi-split heat pumps the measurement and calculations shall be based on the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
Notes on Annex III
Footnotes
- f1
The wet bulb temperature condition is not required when testing units which do not evaporate condensate.
- f2
For units designed for heating and cooling mode, the flow rate obtained during the test at standard rating conditions in cooling mode is used.
- f3
Outlet temperatures dependent on water flow rate as determined at standard rating conditions (100 % part load ratio when cooling, 88 % when heating)
- f4
With the water flow rate determined during ‘A’ test for units with a fixed water flow rate or with a variable flow rate.
- f5
With the water flow rate determined during ‘A’ test for units with a fixed water flow rate or with a variable flow rate.