Article 37 Special protection schemes
United Kingdom
Where a TSO uses a special protection scheme, it shall:
- (a)
ensure that each special protection scheme acts selectively, reliably and effectively;
- (b)
evaluate, when designing a special protection scheme, the consequences for the transmission system in the event of its incorrect functioning, taking into account the impact on TSOs concerned;
- (c)
verify that the special protection scheme has a comparable reliability to the protection systems used for the primary protection of transmission system elements;
- (d)
operate the transmission system with the special protection scheme within the operational security limits determined in accordance with Article 25; and
- (e)
coordinate special protection scheme functions, activation principles and setpoints with F1... affected transmission-connected DSOs, including closed distribution systems and affected transmission-connected SGUs.
Annotations
Textual amendments
- F1
Words in Art. 37(e) omitted (E.W.S.) (31.12.2020) by virtue of The Electricity Network Codes and Guidelines (System Operation and Connection) (Amendment etc.) (EU Exit) Regulations 2019 (S.I. 2019/533), reg. 1(2), Sch. 1 para. 33 (as amended by S.I. 2020/1016, regs. 1(2), 6(2)); 2020 c. 1, Sch. 5 para. 1(1)