Article 114 Requirements for fixed foam fire extinguishing installations
In every vessel to which these Rules apply every fixed foam fire extinguishing installation shall be capable of discharging through fixed discharge outlets in not more than 5 minutes a quantity of foam sufficient to cover to a depth of 152 millimetres the largest single area over which oil fuel is liable to spread. This installation shall be capable of generating foam suitable for extinguishing oil fires and means shall be provided for the effective distribution of the foam through a permanent system of piping and control valves or cocks to discharge outlets, and for the foam to be effectively directed by fixed sprayers on other main oil fire hazards in the protected space either simultaneously or separately. The installation shall include mobile sprayers ready for immediate use in the firing area of the boiler and in the vicinity of the oil fuel unit.
In every such vessel every fixed foam fire extinguishing installation shall be so arranged that a fire in any of the spaces it protects will not render the controls inaccessible or put the installation out of action.
In every such vessel operating instructions in clear and permanent lettering shall be affixed to every fixed foam fire extinguishing installation or in a position adjacent thereto.