Part II
Table 1a:
Containment Measures for Activities Involving Genetic Modification of Micro-organisms in Laboratories
| Containment Measures | Containment Levels | ||||
|---|---|---|---|---|---|
| 1 | 2 | 3 | 4 | ||
| NOTES
| |||||
| 1 | Laboratory suite: isolation (Note 1) | not required | not required | required | required |
| 2 | Laboratory: sealable for fumigation | not required | not required | required | required |
| Equipment | |||||
| 3 | Surfaces impervious to water, resistant to acids, alkalis, solvents, disinfectants and decontamination agents and easy to clean | required for bench | required for bench | required for bench and floor | required for bench, floor ceiling and walls |
| 4 | Entry to lab via airlock (Note 2) | not required | not required | required where and to extent the risk assessment shows it is required | required |
| 5 | Negative pressure relative to the pressure of the immediate surroundings | not required | required where and to extent the risk assessment shows it is required | required | required |
| 6 | Extract and input air from the laboratory shall be HEPA filtered | not required | not required | HEPA filters required for extract air | HEPA filters required for input and extract air (Note 3) |
| 7 | Microbiological safety cabinet/enclosure | not required | required where and to extent the risk assessment shows it is required | required, and all procedures with infective materials required to be contained within a cabinet/enclosure | Class III cabinet required |
| 8 | Autoclave | required on site | required in the building | required in the laboratory suite (Note 4) | double ended autoclave required in laboratory |
| System of work | |||||
| 9 | Access restricted to authorised personnel only | not required | required | required | required (via airlock key procedure) |
| 10 | Specific measures to control aerosol dissemination | not required | required so as to minimise | required so as to prevent | required so as to prevent |
| 11 | Shower | not required | not required | required where and to extent the risk assessment shows it is required | required |
| 12 | Protective clothing | suitable protective clothing required | suitable protective clothing required | suitable protective clothing required; footwear required where and to extent the risk assessment shows it is required | complete change of clothing and footwear required before entry and exit |
| 13 | Gloves | not required | required where and to extent the risk assessment shows they are required | required | required |
| 14 | Efficient control of disease vectors (eg rodents and insects) which could disseminate GMMs | required where and to extent the risk assessment shows it is required | required | required | required |
| 15 | Specified disinfection procedures in place | required where and to extent the risk assessment shows they are required | required | required | required |
| Waste | |||||
| 16 | Inactivation of GMMs in effluent from handwashing sinks and showers and similar effluents | not required | not required | required where and to extent the risk assessment shows it is required | required |
| 17 | Inactivation of GMMs in contaminated material and waste | required by validated means | required by validated means | required by validated means | required by validated means |
| Other measures | |||||
| 18 | Laboratory to contain its own equipment | not required | not required | required, so far as is reasonably practicable | required |
| 19 | An observation window or alternative is to be present so that occupants can be seen | required where and to extent the risk assessment shows it is required | required where and to extent the risk assessment shows it is required | required | required |
| 20 | Safe storage of GMMs | required where and to extent the risk assessment shows it is required | required | required | secure storage required |
| 21 | Written records of staff training | not required | required where and to extent the risk assessment shows they are required | required | required |
Table 1b:
Containment Measures for Activities Involving Genetic Modification of Micro-organisms in Plant Growth Facilities (to be read with Table 1a as indicated in paragraph 3)
| Containment Measures | Containment Levels | Additional/modification | ||||
|---|---|---|---|---|---|---|
| 1 | 2 | 3 | 4 | |||
| NOTE
| ||||||
| Building | ||||||
| 1 | Permanent structure (Note 1) | required where and to extent the risk assessment shows it is required | required | required | required | Modification |
| Equipment | ||||||
| 2 | Entry via a separate room with two interlocking doors | not required | required where and to extent the risk assessment shows it is required | required where and to extent the risk assessment shows it is required | required (via airlock key procedure) | Additional |
| 3 | Control of contaminated run-off water | required where and to extent the risk assessment shows it is required | required so as to prevent run-off | required so as to prevent run-off | required so as to prevent run-off | Additional |
| System of work | ||||||
| 4 | Effective control of disease vectors such as insects, rodents and arthropods which could disseminate GMMs | required | required | required | required | Additional |
| 5 | Effective control of pollen, seeds and other plant material which could disseminate GMMs | required where and to extent the risk assessment shows it is required | required so as to minimise dissemination | required so as to prevent dissemination | required so as to prevent dissemination | Additional |
| 6 | Procedures for transfer of living material between the plant growth facilities, protective structure and laboratory shall control dissemination of GMMs | required so as to minimise dissemination | required so as to prevent dissemination | required so as to prevent dissemination | required so as to prevent dissemination | Additional |
Table 1c:
Containment Measures for Activities Involving Genetic Modification of Micro-organisms in Animal Units (to be read with Table 1a as indicated in paragraph 3)
| Containment Measures | Containment Levels | Additional/modification | ||||
|---|---|---|---|---|---|---|
| 1 | 2 | 3 | 4 | |||
| NOTES
| ||||||
| Facilities | ||||||
| 1 | Isolation of animal unit (Note 1) | required where and to extent the risk assessment shows it is required | required | required | required | Modification |
| 2 | Animal facilities (Note 2) separated by lockable doors | required where and to extent the risk assessment shows they are required | required | required | required | Additional |
| 3 | Animal facilities (cages, etc) designed to facilitate decontamination (waterproof and easily washable material) | required where and to extent the risk assessment shows they are required | required where and to extent the risk assesment shows they are required | required | required | Additional |
| 4 | Floor, walls and ceiling easily washable | required where and to extent the risk assessment shows they are required | required for floor | required for floor and walls | required for floor, walls and ceiling | Modification |
| 5 | Appropriate filters on isolators or isolated rooms (Note 3) | not required | required where and to extent the risk assessment shows they are required | required | required | Additional |
| 6 | Incinerator for disposal of animal carcasses | required to be accessible | required to be accessible | required to be accessible | required to be on site | Additional |
| 7 | Appropriate barriers at the room exit, and at drains or ventilation duct work | required | required | required | required | Additional |
| 8 | Animals kept in appropriate containment facilities, such as cages, pens, tanks or isolators | required where and to extent the risk assessment shows it is required | required where and to extent the risk assessment shows it is required | required where and to extent the risk assessment shows it is required | required where and to extent the risk assessment shows it is required | Additional |
Table 2:
Containment Measures for Activities Involving Genetic Modification of Micro-organisms in Premises other than those referred to in Tables 1a, 1b and 1c
| Containment Measures | Containment Levels | ||||
|---|---|---|---|---|---|
| 1 | 2 | 3 | 4 | ||
| General | |||||
| 1 | Viable micro-organisms shall be contained in a system which separates the process from the workplace and wider environment (closed system) | required where and to extent the risk assessment shows it is required | required | required | required |
| 2 | Closed systems located within a controlled area | not required | required where and to extent the risk assessment shows they are required | required | required and required to be purpose built |
| 3 | Control of exhaust gases from the closed system | not required | required so as to minimise release | required so as to prevent release | required so as to prevent release |
| 4 | Control of aerosols during sample collection, addition of material to a closed system or transfer of material to another closed system | required where and to extent the risk assessment shows it is required | required so as to minimise release | required so as to prevent release | required so as to prevent release |
| 5 | Inactivation of bulk culture fluids before removal from the closed system | required where and to extent the risk assessment shows it is required | required by validated means | required by validated means | required by validated means |
| 6 | Seals shall be designed so as to minimise or prevent release | not required | required so as to minimise release | required so as to prevent release | required so as to prevent release |
| 7 | The controlled area designed to contain spillage of the entire contents of the closed system | required where and to extent the risk assessment shows it is required | required where and to extent the risk assessment shows it is required | required | required |
| 8 | The controlled area sealable to permit fumigation | not required | required where and to extent the risk assessment shows it is required | required where and to extent the risk assessment shows it is required | required |
| 9 | Biohazard signs posted | required where and to extent the risk assessment shows it is required | required | required | required |
| Equipment | |||||
| 10 | Entry via airlock | not required | not required | required where and to extent the risk assessment shows it is required | required |
| 11 | Surfaces resistant to water, acids, alkalis, solvents, disinfectants and decontamination agents and easy to clean | required for any bench | required for any bench | required for floor and any bench | required for bench, floor, ceiling and walls |
| 12 | Specific measures to adequately ventilate the controlled areas in order to minimise air contamination | required where and to extent the risk assessment shows they are required | required where and to extent the risk assessment shows they are required | required where and to extent the risk assessment shows they are required | required |
| 13 | The controlled area maintained at an air pressure negative to the immediate surroundings | not required | not required | required where and to extent the risk assessment shows it is required | required |
| 14 | Extract and input air from the controlled area shall be HEPA filtered | not required | not required | required for extract air, optional for input air | required for input and extract air |
| System of work | |||||
| 15 | Access restricted to authorised personnel only | not required | required | required | required |
| 16 | Decontamination and washing facilities provided for personnel | required | required | required | required |
| 17 | Personnel shall shower before leaving the controlled area | not required | not required | required where and to extent the risk assessment shows it is required | required |
| 18 | Personnel shall wear protective clothing | work clothing required | work clothing required | required | complete change required before exit and entry |
| 19 | Written procedures and records of staff training | not required | not required | required | required |
| Waste | |||||
| 20 | Inactivation of GMMs in effluent from handwashing sinks and showers or similar effluents | not required | not required | required where and to extent the risk assessment shows it is required | required |
| 21 | Inactivation of GMMs in contaminated material and waste including those in process effluent before final discharge | required by validated means | required by validated means | required by validated means | required by validated means |