The number of cable circuits must not exceed six.

(2)

The cables comprising Work No. 1(c) must not—

(a)

exceed 600 kilometres in length; and

(b)

be subject to cable protection with an area greater than 624,000 square metres.

(3)

The cables comprising Work No. 2(d) must not—

(a)

exceed 90 kilometres in length; and

(b)

be subject to cable protection with an area greater than 94,000 square metres.

(4)

The cables comprising Work No. 2(e) must not—

(a)

exceed 654 kilometres in length; and

(b)

be subject to cable protection with an area greater than 792,000 square metres.

(5)

The total number of the cable crossings must not exceed—

(a)

32 within the area of Work Nos. 1 and 2(d); and

(b)

54 within the area utilised for Work No. 2(e);

unless otherwise agreed with the MMO.

(6)

The total volume of cable protection must not exceed 2,042,000 cubic metres with a maximum footprint of 2,058,000 square metres.

(7)

The cables and cable circuits comprised in the authorised development must be constructed in accordance with the parameters set out in the pro–rata annex.