Regulation 26 Cargo pump roomsI1

United Kingdom

(1)

Except as otherwise provided in paragraph (2) in every tanker of Class VII(T) of under 500 tons, each cargo pump room and each pump room having a similar hazard shall be provided with either a fixed pressure water-spraying system comply with the requirements of Schedule 2 of Merchant Shipping Notice MSN 1666 or a fixed gas fire-extinguishing system complying with the requirements of Schedule 4 of Merchant Shipping Notice MSN 1666, which shall be operated from a readily accessible position outside the pump room, provided that where the fixed extinguishing system is a gas system—

(a)

the alarm referred to in Schedule 4 in Merchant Shipping Notice MSN 1666 shall be safe for use in flammable cargo vapour/air mixture;

(b)

a notice shall be exhibited at the controls stating that due to electrostatic ignition hazard, the system is to be used only for fire-extinguishing and not for inerting purposes;

(c)

where the extinguishing medium used in the cargo pump room system is also used in systems serving other spaces, the quantity of medium provided or its delivery rate need not be more than the maximum required for the largest compartment.

(2)

In chemical tankers where the fixed fire-extinguishing system referred to in paragraph (1) is a gas system, the concentration shall be as specified in the Code for the Construction and Equipment of Ships carrying Dangerous Chemicals in Bulk.