Paragraph 5 Reports for meters examined and tested

Original text. Later amendments are not shown.

Subject to paragraph 6, where a transformer intended for use with meters but tested separately from those meters, a statement that–

(1)

the transformer referred to in the report is accurately described and whether it is a new or used transformer;

(2)

the transformer has been examined and tested in accordance with Schedule 1;

(3)

the uncertainty of measurement was not greater than& ±0.1%;

(4)

no transformer error was greater than& ±0.5% at any load from 5% to 100% of full load when connected to maximum rated burden or if known, the working burden;