Paragraph 5 Reports for meters examined and tested
Subject to paragraph 6, where a transformer intended for use with meters but tested separately from those meters, a statement that–
(1)
the transformer referred to in the report is accurately described and whether it is a new or used transformer;
(2)
the transformer has been examined and tested in accordance with Schedule 1;
(3)
the uncertainty of measurement was not greater than& ±0.1%;
(4)
no transformer error was greater than& ±0.5% at any load from 5% to 100% of full load when connected to maximum rated burden or if known, the working burden;