Paragraph 7 Multi-rate meters

Original text. Later amendments are not shown.

Induction meters

(1)
(a)

All multi-rate induction meters shall be tested on one rate in accordance with paragraphs 5 and 6. In addition, a further test shall be carried out on each and every other rate at a low load using Method A, Method B or Method C tests and at a high load using Method A test.

(b)

The difference in errors measured on one rate shall not differ from the errors measured on any other rate, for the same load conditions, by more than 1%.

(c)

Every rate change mechanism shall be tested for correct operation with an applied voltage of 90% of the marked voltage of the meter.

Static meters

(2)
(a)

All multi-rate static meters shall be tested on one rate in accordance with paragraphs 5 and 6.

(b)

On multi-rate static meters, where the total units is the sum of all the rates, a further test shall be carried out on each and every other rate at a high load using Method A.

(c)

On multi-rate static meters, where the total units is recorded on one register, only this register is required to be tested in accordance with paragraphs 5 and 6.