Paragraph 10 Insulation property testI1

England, Wales and Scotland

Each meter shall be tested to demonstrate that the insulation of the meter is of a sufficient standard to enable the meter to operate safely and correctly in the conditions in which it could reasonably be expected to be installed and operated.

TABLE 1

Influence quantitiesReference valueTolerance
Ambient temperatureReference temperature or, if not indicated, 23°C.>15°C to <30°C
Meter positionVertical±3°
VoltageReference voltage±1.5%
FrequencyReference frequency of 50Hz±0.5%
Voltage and current waveformSinusoidal formDistortion factor <5%
External magnetic induction at the reference frequency (paragraph 5(4))ZeroInduction value that does not produce a relative error variation of more than ±0.3%

TABLE 2

Test load in terms of marked current
Test number and loadPower factorBasic/maximumMaximum continuousLong rangeShort rangeMeter typePolyphase meter load
1 (high)1Imax100%100%–200% (Note 1)100%–125% (Note 1)Single and polyphaseBalanced
2 (intermediate)1Ib or 125%IbAny load between 25%–75% of the value specified for test number 1 (Note 1)Single and polyphaseBalanced
3 (low)15%Ib1.67% (Note 2)5%5%Single and polyphaseBalanced
4 (inductive)0.5 (Note 3)Ib or Imax100%The same value selected for test number 1Single and polyphaseBalanced
5 (element)1Ib100%The same value selected for test number 1PolyphaseOne phase loaded in turn
6 (inductive) (element)0.5 (Note 3)Ib100%The same value selected for test number 1PolyphaseOne phase loaded in turn
7 (starting-current)10.5%Ib to 1.0%Ib0.5% to 1.0%0.5% to 1.0%0.5% to 1.0%Single and polyphaseBalanced

Note 1 Where a range is given, any value within that inclusive range may be selected.

  • Note 2 For maximum continuously rated prepayment meters, the low load test value may be twice the value shown.

  • Note 3 For test numbers 4 and 6, the inductive power factor shall be between 0.45 and 0.55 inclusive.