Paragraph 9 Margins of errorI1

England, Wales and Scotland

(1)

The error permitted for—

(a)

single phase and polyphase whole current meters and

(b)

single phase and polyphase transformer operated meters when tested with transformers connected

shall not exceed plus or minus 1.9 per cent. for test numbers 1, 2, 3 and 4 in table 2.

(2)

The error permitted for both single phase and polyphase transformer operated meters, when tested without transformers connected, shall not exceed plus or minus 1.4 per cent. for test numbers 1, 2, 3 and 4 given in table 2.

(3)

The error permitted for polyphase whole current meters and transformer operated meters, when tested with transformers connected, shall not exceed plus 2 per cent. or minus 3 per cent. for test numbers 5 and 6 given in table 2.

(4)

The error permitted for polyphase transformer operated meters, when tested without transformers connected, shall not exceed plus 1.5 per cent. or minus 2.5 per cent. for test numbers 5 and 6 given in table 2.

(5)

Where current and voltage transformers are intended to be used with meters and are not tested connected to a meter then the error of the transformers at any load point throughout the rated range shall not exceed 0.5 per cent.

TABLE 1

Influence quantitiesReference valueTolerance
Ambient temperatureReference temperature or, if not indicated, 23°C.±2°
Meter positionVertical±3°
VoltageReference voltage±1.5%
FrequencyReference frequency of 50Hz±0.5%
Voltage and current waveformSinusoidal formDistortion factor <5%
External magnetic induction at the reference frequency (paragraph 5(5))ZeroInduction value that does not produce a relative error variation of more than ±0.3%

TABLE 2

Test load in terms of marked current
Test number and loadPower factorBasic/maximumMaximum continuousLong rangeShort rangeMeter typePolyphase meter load
1 (high)1Imax100%100%–200%(Note 1)100%–125% (Note 1)Single and polyphaseBalanced
2 (intermediate)1Ib or 125%IbAny load between 25%–75% of the value specified for test number 1 (Note 1)Single and polyphaseBalanced
3 (low)15%Ib1.67% (Note 2)5%5%Single and polyphaseBalanced
4 (inductive)0.5 (Note 3)Ib or Imax100%The same value selected for test number 1Single and polyphaseBalanced
5 (element)1Ib100%The same value selected for test number 1 Polyphase One phase loaded in turn
6 (inductive) (element)0.5 (Note 3)Ib100%The same value selected for test number 1PolyphaseOne phase loaded in turn

Note 1 Where a range is given, any value within that inclusive range may be selected.

  • Note 2 For maximum continuously rated prepayment meters, the low load test value may be twice the value shown.

  • Note 3 For test numbers 4 and 6, the inductive power factor shall be between 0.45 and 0.55 inclusive.