Paragraph 9 Margins of ErrorI1
Northern Ireland
The maximum error permitted for—
single phase and polyphase whole current meters; and
single phase and polyphase transformer operated meters when tested with transformers connected
shall not exceed plus or minus 1.5% for tests numbers 1, 2, 3 and 4 given in Table 2.
The maximum error permitted for both single phase and polyphase transformer operated meters, when tested without transformers connected, shall not exceed plus or minus 1.0% for tests numbers 1, 2, 3 and 4 given in Table 2.
The maximum error permitted for polyphase whole current and transformer operated meters, when tested with transformers connected, shall not exceed plus 1.7% or minus 2.7% for tests 5 and 6 given in Table 2.
The maximum error permitted for polyphase transformer operated meters, when tested without transformers connected, shall not exceed plus 1.2% or minus 2.2% for test numbers 5 and 6 given in Table 2.
Where current and voltage transformers, which are intended to be used with meters, are not tested connected to a meter then the total error of the transformers at any load point throughout the rated range shall not exceed 0.5%.