Paragraph 1 I1
Northern Ireland
In respect of each meter to which the report refers, a statement—
that the meter referred in the report is accurately described and whether it is a new or repaired meter;
that the meter has been examined and tested in accordance with Schedule 1 or one of the equivalent European provisions;
that the uncertainty of measurement was not greater than ±0.4% at unity power factor or greater than ±0.6% at 0.5 inductive power factor;
that no meter error was greater than any error specified either in the relevant sub-paragraph of paragraph 9 of Schedule 1 or in one of the equivalent European provisions;
that the meter did not register when energised on voltage only, whether with or without a current less than the threshold current; and
if applicable, as to whether paragraph 1(2) of Schedule 1 did or did not apply (as the case may be).