The maximum error permitted for—
single phase and polyphase whole current meters; and
single phase and polyphase transformer operated meters when tested with transformers connected
shall not exceed plus or minus 1.9% for test numbers 1, 2, 3 and 4 in Table 2.
The maximum error permitted for both single phase and polyphase transformer operated meters, when tested without transformers connected, shall not exceed plus or minus 1.4% for test numbers 1, 2, 3 and 4 given in Table 2.
The maximum error permitted for polyphase whole current meters and transformer operated meters, when tested with transformers connected, shall not exceed plus 2% or minus 3% for test numbers 5 and 6 given in Table 2.
The maximum error permitted for polyphase transformer operated meters, when tested without transformers connected, shall not exceed plus 1.5% or minus 2.5% for test numbers 5 and 6 given in Table 2.
Where current and voltage transformers, which are intended to be used with meters, are not tested connected to a meter then the total error of the transformers at any load point throughout the rated range shall not exceed 0.5%.
TABLE 1
| Influence Quantities | Reference Value | Tolerance |
|---|---|---|
| Ambient temperature | Reference temperature or, if not indicated, 23°C. | ± 2° |
| Meter Position | Vertical | ± 3° |
| Voltage | Reference voltage | ± 1.5% |
| Frequency | Reference frequency 50Hz | ± 0.5% |
| Voltage and current waveform | Sinusoidal form | Distortion factor <5% |
| External magnetic induction at the reference frequency | Zero | Induction value that does not produce a relative error variation of more than ±0.3% |
TABLE 2
| Test load in terms of marked current | |||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Test Number and Load | Power Factor | Basic/Maximum | Maximum continuous | Long Range | Short Range | Meter Type | Polyphase Meter Load | ||||||
| |||||||||||||
| 1 (high) | 1 | Imax | 100% | 100%-200% (Note 1) | 100%-125% (Note 1) | Single and polyphase | Balanced | ||||||
| 2 (intermediate) | 1 | Ib or 125% Ib | Any load between 25%-75% of the value specified for Test Number 1 | Single and polyphase | Balanced | ||||||||
| 3 (low) | 1 | 5% Ib | 1,67% (Note 2) | 5% | 5% | Single and polyphase | Balanced | ||||||
| 4 (inductive) | 0.5 (Note 3) | Ib or Imax | 100% | The same value selected for Test Number 1 | Single and polyphase | Balanced | |||||||
| 5 (element) | 1 | Ib | 100% | The same value selected for Test Number 1 | Polyphase | One phase loaded in turn | |||||||
| 6 (inductive) (element) | 0.5 (Note 3) | Ib | 100% | The same value selected for Test Number 1 | Polyphase | One phase loaded in turn | |||||||