Paragraph 6 Detailed design parameters onshore
(1)
The onshore works must not exceed the parameters set out in the following table and sub-paragraph (2)—
| (1) Parameter | (2) Value |
|---|---|
| Maximum number of landfall transition joint bays | 2 |
(2)
In relation to Work No. 11 (onshore substation)—
(a)
the highest part of any building, any external electrical equipment or enclosure, excluding lightning rods, must not exceed a height of 13m above Ordnance Datum;
(b)
the total area of the fenced compound (excluding its accesses) must not exceed 58,800m2; and
(c)
the lightning rods within the fenced compound must not exceed a height of 18m above Ordnance Datum.