Paragraph 2 Frequency of sampling for Group A parametersF1
United Kingdom
Monitoring for a Group A parameter must be undertaken at the frequencies specified in Table 2.
Table 2
Sampling frequency for Group A parameters
| Volume m3/day | Sampling frequency per year |
|---|---|
| ≤ 10 | 1 |
| > 10 ≤ 100 | 2 |
| > 100 ≤ 1,000 | 4 |
| > 1,000 ≤ 2,000 | 10 |
| > 2,000 ≤ 3,000 | 13 |
| > 3,000 ≤ 4,000 | 16 |
| > 4,000 ≤ 5,000 | 19 |
| > 5,000 ≤ 6,000 | 22 |
| > 6,000 ≤ 7,000 | 25 |
| > 7,000 ≤ 8,000 | 28 |
| > 8,000 ≤ 9,000 | 31 |
| > 9,000 ≤ 10,000 | 34 |
| > 10,000 | 4 + 3 for each 1,000m3/day of the total volume (rounding up to the nearest multiple of 1,000m3/day) |
Annotations
Textual amendments
- F1
Sch. 2 Pts. 1-2A substituted for Sch. 2 Pts. 1-2 (11.7.2018) by The Private Water Supplies (England) (Amendment) Regulations 2018 (S.I. 2018/707), regs. 1(1), 2(10)(a) (with reg. 3)