Table 1
Prescribed methods of analysis
| Parameter | Method |
|---|---|
| Clostridium perfringens (including spores) | F1BS-EN ISO 14189 |
| Coliform bacteria and F2E. coli | BS-EN ISO 9308-1 and BS-EN ISO 9308-2 |
Colony count 22°C-enumeration of culturable microorganisms | BS-EN ISO 6222 |
Colony count 37°C-enumeration of culturable microorganisms | BS-EN ISO 6222 |
| Enterococci | BS-EN ISO 7899-2 |
| Pseudomonas aeruginosa | F3BS-EN ISO 16266 |
F4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
F5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
F6Table 3
Minimum performance characteristic: uncertainty of measurement
| Parameters | Uncertainty of measurement % of the parametric value (except for pH) (1) |
|---|---|
(1) “Uncertainty of measurement” is a non-negative parameter characterising the dispersion of the quantity values being attributed to a measurement, based on the information used. The performance criterion for measurement uncertainty (k = 2) is the percentage of the parametric value stated in the table or better. Measurement uncertainty must be estimated at the level of the parametric value. | |
(2) If the value of uncertainty of measurement cannot be met, the best available technique must be selected (up to 60% of the parametric value). | |
(3) The method determines total cyanide in all forms. | |
(4) Reference method: European standard EN ISO 8467 entitled “Water quality - Determination of permanganate index (ISO 8467:1993). | |
(5) The performance characteristics for individual pesticides are given as an indication. Values for the uncertainty of measurement as low as 30% can be achieved for several pesticides, higher values up to 80% may be allowed for a number of pesticides. | |
(6) The performance characteristics apply to individual substances, specified at 25% of the parametric value in Part 1 of Table B in Part 1 of Schedule 1. | |
(7) The performance characteristics apply to individual substances, specified at 50% of the parametric value in Part 1 of Table B in Part 1 of Schedule 1. | |
(8) The uncertainty of measurement must be estimated at the level of 3 mg/l of the total organic carbon (TOC) in accordance with European standard EN 1484 entitled “Water analysis - Guidelines for the determination of total organic carbon and dissolved organic carbon” and dissolved organic carbon (DOC) must be used. | |
(9) The uncertainty of measurement must be estimated at the level of 1.0 nephelometric turbidity units (NTU) in accordance with European standard EN ISO 7027-1 entitled “Water quality - Determination of turbidity - Part 1: Quantitative methods (ISO 7027-1:2016”. | |
| Aluminium | 25 |
| Ammonium | 40 |
| Antimony | 40 |
| Arsenic | 30 |
| Benzene | 40 |
| Benzo(a)pyrene (2) | 50 |
| Boron | 25 |
| Bromate | 40 |
| Cadmium | 25 |
| Chloride | 15 |
| Chromium | 30 |
| Colour | 20 |
| Conductivity | 20 |
| Copper | 25 |
| Cyanide (3) | 30 |
| 1,2-dichloroethane | 40 |
| Fluoride | 20 |
| Hydrogen ion concentration pH (expressed in pH units) | 0.2 |
| Iron | 30 |
| Lead | 25 |
| Manganese | 30 |
| Mercury | 30 |
| Nickel | 25 |
| Nitrate | 15 |
| Nitrite | 20 |
| Oxidisability (4) | 50 |
| Pesticides (5) | 30 |
| Polycyclic aromatic hydrocarbons (6) | 50 |
| Selenium | 40 |
| Sodium | 15 |
| Sulphate | 15 |
| Tetracloroethene (7) | 30 |
| Tetracloromethane | 30 |
| Trichloroethene (7) | 40 |
| Trihalomethanes: total (6) | 40 |
| Total organic carbon (8) | 30 |
| Turbidity (9) | 30 |
Annotations
Textual amendments
- F1
Words in Sch. 3 Pt. 2 substituted (11.7.2018) by The Private Water Supplies (England) (Amendment) Regulations 2018 (S.I. 2018/707), regs. 1(1), 2(11)(c)(i) (with reg. 3)
- F2
Words in Sch. 3 Pt. 2 substituted (11.7.2018) by The Private Water Supplies (England) (Amendment) Regulations 2018 (S.I. 2018/707), regs. 1(1), 2(11)(c)(ii) (with reg. 3)
- F3
Words in Sch. 3 Pt. 2 substituted (11.7.2018) by The Private Water Supplies (England) (Amendment) Regulations 2018 (S.I. 2018/707), regs. 1(1), 2(11)(c)(iii) (with reg. 3)
- F4
Sch. 3 Pt. 2 unnumbered table omitted (11.7.2018) by virtue of The Private Water Supplies (England) (Amendment) Regulations 2018 (S.I. 2018/707), regs. 1(1), 2(11)(d)(i) (with reg. 3)
- F5
Sch. 3 Pt. 2 Table 2 omitted (11.7.2018) by virtue of The Private Water Supplies (England) (Amendment) Regulations 2018 (S.I. 2018/707), regs. 1(1), 2(11)(d)(ii) (with reg. 3)
- F6
Sch. 3 Pt. 2 Table 3 inserted (11.7.2018) by The Private Water Supplies (England) (Amendment) Regulations 2018 (S.I. 2018/707), regs. 1(1), 2(11)(e) (with reg. 3)