Paragraph 8 Performance characteristics and method of analysis.
For the following parameters and radionuclides, the method of analysis used must, as a minimum be capable of measuring activity concentrations with a limit of detection specified below in Table E:
TABLE E
1 The limit of detection must be calculated according to the ISO standard 11929:2010 entitled “Determination of the characteristic limits (decision threshold, detection limit and limits of the confidence interval) for measurements of ionising radiation - Fundamentals and application”, with probabilities of errors of 1st and 2nd kind of 0.05 each. | |
2 Measurement uncertainties must be calculated and reported as complete standard uncertainties, or as expanded standard uncertainties with an expansion factor of 1.96, according to the ISO IEC Guide 98-3:2008 entitled “Guide to the expression of uncertainty in measurement”. | |
3 The limit of detection for tritium and for radon is 10% of the corresponding parametric value of 100 Bg/l. | |
4 The limit of detection for gross alpha activity and gross beta activities is 40% of the screening values of 0.1 Bq/l and 1.0 Bq/l respectively. | |
5 This limit of detection applies only to initial screening for indicative dose for a new water source. If initial checking indicates that it is unlikely that Ra-228 exceeds 20% of the derived concentration, the limit of detection may be increased to 0.08 Bq/l for routine Ra-228 nuclide specific measurements, until a subsequent re-check is required. | |
| Parameters and radiouclides | Limit of detection12 |
|---|---|
| Tritium | 10 Bg/l3 |
| Radon | 10 Bg/l3 |
| gross alpha activity | 0.04 Bg/l4 |
| gross beta activity | 0.4 Bg/l4 |
| U-238 | 0.02 Bg/l |
| U-234 | 0.02 Bg/l |
| Ra-226 | 0.04 Bg/l |
| Ra-228 | 0.02 Bg/l5 |
| Pb-210 | 0.02 Bg/l |
| Po-210 | 0.01 Bg/l |
| C-14 | 20 Bg/l |
| Sr-90 | 0.4 Bg/l |
| Pu-239/Pu-240 | 0.04 Bg/l |
| Am-241 | 0.06 Bg/l |
| Co-60 | 0.5 Bg/l |
| Cs-134 | 0.5 Bg/l |
| Cs-137 | 0.5 Bg/l |
| I-131 | 0.5 Bg/l |