Part 3 Minimum frequency for both monitoring for Group A parameters and monitoring for Group B parameters for water put into bottles or containersI1
England and Wales
| Volumea of water produced in bottles or containers each day (m3) | Monitoring for Group A parameters: number of samples per year | Monitoring for Group B parameters: number of samples per year |
|---|---|---|
| ≤10 | 1 | 1 |
| ˃ 10 ≤ 60 | 12 | 1 |
| ˃ 60 | 1 for each 5 m3/day of the total volume (rounding up to the nearest multiple of 5 m3/day) | 1 for each 100 m3/day of the total volume (rounding up to the nearest multiple of 100 m3/day) |
| a The volumes are calculated as averages taken over a calendar year. | ||
Annotations
Commencement
- I1
Sch. 2 Pt. 3 in force at 20.11.2017, see reg. 1