The points of discharge of urban waste water shall be chosen, as far as possible, so as to minimize the effects on receiving waters.

TABLE 1

REQUIREMENTS FOR DISCHARGES FROM URBAN WASTE WATER TREATMENT PLANTS SUBJECT TO REGULATION 7(1) AND (2)

The values for concentration or for the percentage of reduction shall apply.

ParametersConcentrationMinimum percentage of reductionf1Reference method of measurement
(001)

Reduction in relation to the load of the influent.

(002)

The parameter can be replaced by another parameter: total organic carbon (TOC) or total oxygen demand (TOD) if a relationship can be established between BOD5, and the substitute parameter.

Analyses concerning discharges from lagooning shall be carried out on filtered samples; however, the concentration of total suspended solids in unfiltered water samples shall not exceed 150 mg/l.
Biochemical oxygen demand (BOD5 at 20°C) without nitrificationf225 mg/l O270-90Homogenized, unfiltered, undecanted sample. Determination of dissolved oxygen before and after five-day incubation at 20°C ± 1°C, incomplete darkness. Addition of a nitrification inhibitor.
Chemical oxygen demand (COD)125 mg/l O275Homogenized, unfiltered, undecanted sample Potassium dichromate

TABLE 2

REQUIREMENTS FOR DISCHARGES FROM URBAN WASTE WATER TREATMENT PLANTS TO SENSITIVE AREAS WHICH ARE SUBJECT TO EUTROPHICATION AS IDENTIFIED IN SUB-PARAGRAPH (a) OF PART I OF SCHEDULE 1

One or both parameters may be applied depending on the local situation. The values for concentration or for the percentage of reduction shall apply.

ParametersConcentrationMinimum percentage of reductionf3Reference method of measurement
(003)

Reduction in relation to the load of the influent.

(004)

Total nitrogen means: the sum of total Kjeldahl-nitrogen (organic N + NH3), nitrate (NO3)-nitrogen and nitrite (NO2)-nitrogen.

(005)

These values for concentration are annual means as referred to in Schedule 3, Part II, paragraph 4(c). However, the requirements for nitrogen may be checked using daily averages when it is proved, in accordance with Schedule 3, Part II, paragraph 1, that the same level of protection is obtained. In this case, the daily average must not exceed 20 mg/l of total nitrogen for all the samples when the temperature from the effluent in the biological reactor is superior or equal to 12 °C. The conditions concerning temperature could be replaced by a limitation on the time of operation to take account of regional climatic conditions.

Total phosphorus2 mg/l P (10,000-100,000 p.e.) 1 mg/1 P (more than 100,000 p.e.)80Molecular absorption spectrophotometry
Total nitrogenf415 mg/1 N (10,000-100,000 p.e.)(005) 10 mg/1 N (more than 100,000 p.e.)f570-80Molecular absorption spectrophotometry

Annotations

Commencement

I1

Sch. 3 Pt. 1 para. 5 in operation at 1.4.2007, see reg. 1

Footnotes

f1

(001)

Reduction in relation to the load of the influent.

f2

(002)

The parameter can be replaced by another parameter: total organic carbon (TOC) or total oxygen demand (TOD) if a relationship can be established between BOD5, and the substitute parameter.

f3

(003)

Reduction in relation to the load of the influent.

f4

(004)

Total nitrogen means: the sum of total Kjeldahl-nitrogen (organic N + NH3), nitrate (NO3)-nitrogen and nitrite (NO2)-nitrogen.

f5

(005)

These values for concentration are annual means as referred to in Schedule 3, Part II, paragraph 4(c). However, the requirements for nitrogen may be checked using daily averages when it is proved, in accordance with Schedule 3, Part II, paragraph 1, that the same level of protection is obtained. In this case, the daily average must not exceed 20 mg/l of total nitrogen for all the samples when the temperature from the effluent in the biological reactor is superior or equal to 12 °C. The conditions concerning temperature could be replaced by a limitation on the time of operation to take account of regional climatic conditions.