OpenLegislation

Schedule 2 Indicator parameters

1 The water should not be aggressive.

2 Where treatment to reduce the level of radionuclides in water intended for human consumption has been taken, monitoring must be carried out to ensure the continued efficacy of the treatment.

3 Remedial action may be taken by the Secretary of State on radiological protection grounds without further consideration and deemed to be justified where radon concentrates exceed 1,000 Bq/1.

4 If tritium concentration exceeds its parametric value, an investigation (which may include analysis) of the presence of artificial radionuclides is required.

5 May be monitored from samples of water leaving treatment works or other supply point, as no significant change during distribution.

(1)(2)(3)(4)(5)
ItemParametersSpecification concentration or value (maximum unless otherwise stated) or stateUnits of measurementPoint of compliance
1.Ammonium0.50mgNH4/1Consumers' taps
2.Chloride1250mgC1/Supply point5
3.Clostridium0Number/100mlSupply point5

Perfringens

(including spores)

4.Coliform bacteria0Number/100mlConsumers' taps
5.Colony countsNo abnormal changeNumber/1ml at 22°CConsumers' taps, service reservoirs and treatment works
6.Conductivity12500μS/cm at 20°CSupply point5
7.Hydrogen ion

9.5 (maximum)

6.5 (minimum)

pH valueConsumers' taps
8.Indicative dose20.10mSvSupply point5
(a) gross alpha0.1Bq/1Supply point5
(b) gross beta1Bq/1Supply point5
9.Radon3100Bq/1Supply point
10.Sulphate1250mgSO4/lSupply point5
11.Total organic carbon (TOC)No abnormal changemgC/lSupply point
12.Tritium (for radioactivity)4100Bq/lSupply point5
13.Turbidity1NTUTreatment works