OpenLegislation

Schedule 2 INDICATOR PARAMETERSI1I2

Northern Ireland

ItemParametersSpecification Concentration or Value (maximum) or StateUnits of MeasurementPoint of monitoring

Notes:

(i)

The water should not be aggressive.

(ii)

Excluding tritium, potassium-40, radon and radon decay products.

*

May be monitored from samples of water leaving treatment works or other supply point, as no significant change during distribution.

1.Ammonium0.50mgNH4/lConsumers' taps
2.Chloride f1250mgCl/lSupply pointf2
3.Clostridium perfringens (including spores)0Number/100mlSupply point
4.Coliform bacteria0Number/100mlConsumers' taps
5.Colony countsNo abnormal changeNumber/1ml at 22°C Number/1ml at 37°CConsumers' taps, service reservoirs and treatment works
6.Conductivity 2500μS/cm at 20°CSupply point
7.Hydrogen ion9.5pH valueConsumers' taps
8.Sulphate 250mgSO4/lSupply point
9.Total indicative dose (for radioactivity) f30.10mSv/yearSupply point
10.Total organic carbon (TOC)No abnormal changemgC/lSupply point*
11.Tritium (for radioactivity)100Bq/lSupply point
12.Turbidity1NTUTreatment works

Annotations

Commencement

I1

Sch. 2 in operation at 28.11.2002 for specified purposes, see reg. 1(2)

I2

Sch. 2 in operation at 25.12.2003 in so far as not already in operation, see reg. 1(4)

Footnotes

f1

(i)

The water should not be aggressive.

f2

*

May be monitored from samples of water leaving treatment works or other supply point, as no significant change during distribution.

f3

(ii)

Excluding tritium, potassium-40, radon and radon decay products.