Part IV MONITORING
Northern Ireland
TABLE 1.
PARAMETERS AND CIRCUMSTANCES FOR CHECK MONITORING
| (1) | (2) | (3) |
|---|---|---|
| Item | Parameter | Circumstances |
| 1. | Aluminium | When used as flocculant or where the water originates from, or is influenced by, surface waters |
| 2. | Ammonium | |
| 3. | Clostridium perfringens (including spores) | Where the water originates from, or is influenced by, surface waters |
| 4. | Coliform bacteria | |
| 5 | Colony Counts | |
| 6. | Colour | |
| 7. | Conductivity | |
| 8. | Escherichia coli (E. coli) | |
| 9. | Hydrogen ion | |
| 10. | Iron | When used as flocculant or where the water originates from, or is influenced by, surface waters |
| 11. | Manganese | Where the water originates from, or is influenced by, surface waters |
| 12. | Nitrate | When chloramination is practised |
| 13. | Nitrite | When chloramination is practised |
| 14. | Odour | |
| 15. | Taste | |
| 16. | Turbidity |
TABLE 2.
ANNUAL SAMPLING FREQUENCIES: WATER SUPPLY ZONES
| (1) | (2) | (3) | (4) |
|---|---|---|---|
| Substances and parameters subject to check monitoring | Estimated population of water supply zone | Reduced | Standard |
Notes: | |||
* Sampling for these parameters may be within water supply zones or at supply points as specified in Table 3, subject to notes (ii) and ((iii)) below. | |||
(i) Where the population is not an exact multiple of 5,000, the population figure should be rounded up to the nearest multiple of 5,000. | |||
(ii) Check monitoring in water supply zones is required only where chloramination is practised. In other circumstances audit monitoring is required. | |||
(iii) Audit monitoring in water supply zones is required only where sodium hypochlorite is added after water has left the treatment works. In other circumstances, audit monitoring is required at supply points. | |||
(iv) To monitor for total indicative dose (for radioactivity). | |||
| E. coli } | <100 | 4 | |
Coliform bacteria } Residual disinfectant } | ≥100 | 12 per 5,000 population f1 | |
| Aluminium } | |||
| Ammonium } | |||
| Clostridium perfringens } | |||
| (including spores)f2 } | |||
| Colony counts } | |||
| Colour } | <100 | 1 | 2 |
| Conductivity } | 100–4,999 | 2 | 4 |
| Hydrogen ion } | 5,000–9,999 | 6 | 12 |
| Iron } | 10,000–29,999 | 12 | 24 |
| Manganese } | 30,000–49,999 | 18 | 36 |
| Nitrate f3 } | 50,000–79,999 | 26 | 52 |
| Nitrite } | 80,000–100,000 | 38 | 76 |
| Odour } | |||
| Taste } | |||
| Turbidity } | |||
| Parameters subject to audit monitoring | |||
| Aluminium } | |||
| Antimony } | |||
| Arsenic } | |||
| Benzene } | |||
| Benzo(a)pyrene } | |||
| Boron } | |||
| Bromate f4 } | |||
| Cadmium } | |||
| Chromium } | |||
| Copper } | |||
| Cyanide } | |||
| 1,2 dichloroethane } | <100 | 1 | |
| Enterococci } | 100–4,999 | 4 | |
| Fluoride } | 5,000–100,000 | 8 | |
| Iron } | |||
| Lead } | |||
| Manganese } | |||
| Mercury } | |||
| Nickel } | |||
| Nitrate } | |||
| Nitrite } | |||
| Pesticides and related products } | |||
| Polycyclic aromatic hydrocarbons } | |||
| Selenium } | |||
| Sodium } | |||
| Trichloroethene/Tetrachloroethene } | |||
| Tetrachloromethane } | |||
| Trihalomethanes } | <100 | 1 | |
| Chloride } | 100–4,999 | 4 | |
| Sulphate } | 5,000–100,000 | 8 | |
| Total organic carbon } | |||
| Tritium } | |||
| Gross alpha f5 } | |||
| Gross beta } | |||
TABLE 3.
ANNUAL SAMPLING FREQUENCIES: TREATMENT WORKS OR SUPPLY POINTS
| (1) | (2) | (3) | (4) | (5) |
|---|---|---|---|---|
| Item | Substances and parameters | Volume of water supplied m3/d | Reduced | Standard |
Notes: | ||||
* Sampling is at treatment works for the substances and parameters shown in column (1) of the Table as items 1 to 6 and at supply points for the other substances and parameters, except nitrite, subject to notes (ii) and (iii); | ||||
(i) Check monitoring is required only in respect of surface waters (see regulation 6(2) and Table 1 in Schedule 3). | ||||
(ii) Sampling at treatment works when chloramination is practised. | ||||
(iii) Sampling at treatment works when chloromination is not practised. | ||||
(iv) Audit monitoring at supply points is required only where sodium hypochlorite is not added after water has left the treatment works. In other circumstances, audit monitoring is required in water supply zones. | ||||
(v) To monitor for total indicative dose (for radioactivity). | ||||
| 1. | E. coli } | <20 | 4 | |
| 2. | Coliform bacteria } | 20–1,999 | 12 | 52 |
| 3. | Colony counts } | 2,000–5,999 | 52 | 104 |
| 4. | Nitrite f6 } | 6,000–11,999 | 104 | 208 |
| 5. | Residual disinfectant } | ≥12,000 | 104 | 365 |
| 6. | Turbidity } | |||
| Subject to check monitoring | ||||
| 7. | Clostridium perfringens f7 } | <20 | 2 | |
| } | 20–999 | 2 | 4 | |
| 8. | Conductivity } | 1,000–1,999 | 6 | 12 |
| } | 2,000–5,999 | 12 | 24 | |
| } | 6,000–9,999 | 18 | 36 | |
| } | 10,000–15,999 | 26 | 52 | |
| } | 16,000–32,999 | 52 | 104 | |
| } | 33,000–49,999 | 78 | 156 | |
| } | 50,000–67,999 | 104 | 208 | |
| } | 68,000–84,999 | 130 | 260 | |
| } | 85,000–101,999 | 156 | 312 | |
| } | 102,000–119,999 | 183 | 365 | |
| } | 120,000–241,999 | 365 | 730 | |
| } | 242,000–484,999 | 730 | 1,460 | |
| } | 485,000–728,999 | 1,095 | 2,190 | |
| Subject to audit monitoring | ||||
| 9. | Benzene } | |||
| 10. | Boron } | |||
| 11. | Bromate f8 } | |||
| 12. | Cyanide } | |||
| 13. | 1,2 dichloroethane } | <20 | 1 | |
| 14. | Fluoride } | 20–999 | 4 | |
| 15. | Mercury } | 1,000–49,999 | 8 | |
| 16. | Nitrite f9 } | 50,000–89,999 | 12 | |
| 17. | Pesticides and } | 90,000–299,999 | 24 | |
| related products } | 300,000–649,999 | 36 | ||
| 18. | Trichloroethene } | ≥650,000 | 48 | |
| Tetrachloroethene } | ||||
| 19. | Tetrachloromethane } | |||
| 20. | Chloride } | |||
| 21. | Sulphate } | |||
| 22. | Total organic carbon } | |||
| 23. | Tritium } | |||
| 24. | Gross alpha f10 } | |||
| 25. | Gross beta } | |||
Annotations
Footnotes
- f1
(i)
Where the population is not an exact multiple of 5,000, the population figure should be rounded up to the nearest multiple of 5,000.
- f2
*
Sampling for these parameters may be within water supply zones or at supply points as specified in Table 3, subject to notes (ii) and ((iii)) below.
- f3
(ii)
Check monitoring in water supply zones is required only where chloramination is practised. In other circumstances audit monitoring is required.
- f4
(iii)
Audit monitoring in water supply zones is required only where sodium hypochlorite is added after water has left the treatment works. In other circumstances, audit monitoring is required at supply points.
- f5
(iv)
To monitor for total indicative dose (for radioactivity).
- f6
(ii)
Sampling at treatment works when chloramination is practised.
- f7
(i)
Check monitoring is required only in respect of surface waters (see regulation 6(2) and Table 1 in Schedule 3).
- f8
(iv)
Audit monitoring at supply points is required only where sodium hypochlorite is not added after water has left the treatment works. In other circumstances, audit monitoring is required in water supply zones.
- f9
(iii)
Sampling at treatment works when chloromination is not practised.
- f10
(v)
To monitor for total indicative dose (for radioactivity).