OpenLegislation

Paragraph 1

A water undertaker may use a screening strategy for gross alpha and gross beta to monitor for the parametric indicator value for indicative dose M1. The recommended screening value for gross alpha is 0.1Bq/l and for gross beta is 1.0Bq/l.

If the gross alpha activity exceeds 0.1Bq/l or the gross beta activity exceeds 1.0Bq/l, analysis for specific radionuclides is required.

The radionuclides to be measured must be based on all relevant information about likely sources of radioactivity.

Annotations

Marginal citations

M1

Where appropriate gross beta activity may be replaced by residual beta activity after subtraction of the K-40 activity concentration.