Part 3 UNIT Y PARAMETERSI1

England and Wales

Table 15

ComponentWork No.Maximum length (m)Maximum width (m)Maximum height (m AGL)Maximum height (m AOD)
Turbine hall building2A(ii)92232834
Heat recovery steam generator building (up to two)2A(iv)55294955
Exhaust gas emission flue stacks (up to two)2A(iv)––123129
Bypass stack (up to two)2A(v)––123129
Transformers2A(vi)36201117
Gas turbine air inlet filter house2A(vii)26273541
Power control centre2A(viii)1717612
Fuel gas station (up to two)2A(xv)2619713
Main pipe rack2B(i)1100122531
Battery storage facility including any structure (where constructed in two stages being stage 1 and stage 2)3B90601016
Gas insulated switchgear banking building or extension to 4A building4B18121117
Sludge lagoon (up to two)12B8255––
Cable Sealing End Compound8B(ii)35282026

Table 16

ComponentWork No.Minimum height (m AGL)Minimum height (m AOD)
Exhaust gas emission flue stack (up to two)2A(iv)122.5128.5
Bypass stack (up to two)2A(v)122.5128.5