Paragraph 12 Detailed design parameters onshoreI1
England, Wales and Scotland
The total number of buildings housing the principal electrical equipment for an onshore substation comprised in Work No.67 must not exceed two.
Construction works for the buildings referred to in paragraph (1) above must not commence until details of the layout, scale and external appearance of the same have been submitted to and approved by the relevant planning authority. The onshore substations must be carried out in accordance with the approved details.
Any details provided by the undertaker pursuant to paragraph (2) must accord with the design and access statement and be within the Order limits.
Buildings comprised in Work No. 67 must not exceed a height of 25 metres above existing ground level and external electrical equipment comprised in Work No. 67 must not exceed a height of 15 metres above existing ground level.
For the purposes of this requirement ‘existing ground level’ means 54 metres above ordnance datum.
The total footprint of the buildings housing the principal electrical equipment for an onshore substation comprised in Work No. 67 must not exceed 116 metres in length and 85 metres in width.
The fenced compound area (excluding its accesses) for the onshore substations comprised in Work No. 67 must not exceed 3.04ha.
In relation to the kiosks to be located within the onshore cable corridor—
No stage of the connection works may commence until for that stage details of the scale and appearance of the kiosks have been submitted to and approved in writing by the relevant planning authority;
the footprint of each kiosk must not exceed 1 metre in width, 0.75 metres in length and 1 metre in height; and
the kiosks must be constructed in accordance with the approved details.
The footprint of the construction consolidation sites must not exceed the following—
3,600 m2 in the case of a primary construction consolidation site; or
1,200 m2 in the case of a secondary construction consolidation site.
In the event that Work No. 67 is to be carried out in two onshore phases neither phase must comprise more than one onshore substation.
The footprint of each jointing bay compound must not exceed 3,740 m2.
The total length of the haul road must not exceed 18.05 kilometres.