Paragraph 1.5.1 Requirements in respect of safety-related devices
Northern Ireland Not yet in force
Safety devices must function independently of any measurement or control devices required for operation.
As far as possible, failure of a safety device must be detected sufficiently rapidly by appropriate technical means to ensure that there is only very little likelihood that dangerous situations will occur.
For electrical circuits the fail-safe principle is to be applied in general.
Safety-related switching must in general directly actuate the relevant control devices without intermediate software command.