Division BAT 5 BAT is to monitor emissions to water from flue-gas treatment with at least the frequency given below and in accordance with EN standards. If EN standards are not available, BAT is to use ISO, national or other international standards that ensure the provision of data of an equivalent scientific quality.

United Kingdom

Original text. Later amendments are not shown.

TOC monitoring and COD monitoring are alternatives. TOC monitoring is the preferred option because it does not rely on the use of very toxic compounds.

Substance/ParameterStandard(s)Minimum monitoring frequencyMonitoring associated with
Total organic carbon (TOC)f1 EN 1484Once every monthBAT 15
Chemical oxygen demand (COD) No EN standard available
Total suspended solids (TSS)EN 872
Fluoride (F–)EN ISO 10304-1
Sulphate (SO4 2–)EN ISO 10304-1
Sulphide, easily released (S2–)No EN standard available
Sulphite (SO3 2–)EN ISO 10304-3
Metals and metalloidsAsVarious EN standards available (e.g. EN ISO 11885 or EN ISO 17294-2)
Cd
Cr
Cu
Ni
Pb
Zn
HgVarious EN standards available (e.g. EN ISO 12846 or EN ISO 17852)
Chloride (Cl–)Various EN standards available (e.g. EN ISO 10304-1 or EN ISO 15682)—
Total nitrogenEN 12260—

Annotations

Footnotes

f1

TOC monitoring and COD monitoring are alternatives. TOC monitoring is the preferred option because it does not rely on the use of very toxic compounds.