Division Averaging periods and reference conditions for emissions to air
United Kingdom
Unless stated otherwise, the emission levels associated with the best available techniques (BAT-AELs) for emissions to air given in these BAT conclusions refer to values of concentration, expressed as mass of emitted substance per volume of waste gas under standard conditions (dry gas at a temperature of 273,15 K, and a pressure of 101,3 kPa), and expressed in the unit mg/Nm3.
Unless stated otherwise, the averaging periods associated with the BAT-AELs for emissions to air are defined as follows.
| For any parameter where, due to sampling or analytical limitations, 30-minute sampling is inappropriate, a suitable sampling period is employed. | ||
| For PCDD/F, a sampling period of 6 to 8 hours is used. | ||
| Type of measurement | Averaging period | Definition |
|---|---|---|
| Continuous | Daily average | Average over a period of 1 day based on valid hourly or half-hourly averages |
| Periodic | Average over the sampling period | Average of three consecutive measurements of at least 30 minutes eachf1 f2 |
Where BAT-AELs refer to specific emission loads, expressed as load of emitted substance per unit of production output, the average specific emission loads ls are calculated using Equation 1:
| Equation 1: |
where:
number of measurement periods;
average concentration of the substance during ith measurement period;
average flow rate during ith measurement period;
production output during ith measurement period.
Annotations
Footnotes
- f1
-
For any parameter where, due to sampling or analytical limitations, 30-minute sampling is inappropriate, a suitable sampling period is employed.
- f2
-
For PCDD/F, a sampling period of 6 to 8 hours is used.