Division 2 COMBINATION HEATERS

United Kingdom

Original text. Later amendments are not shown.

For combination heaters, the technical documentation referred to in Article 3(2)(c) shall include:

  1. (a)

    the name and address of the supplier;

  2. (b)

    a description of the combination heater model sufficient for its unambiguous identification;

  3. (c)

    where appropriate, the references of the F1designated standards applied;

  4. (d)

    where appropriate, the other technical standards and specifications used;

  5. (e)

    the identification and signature of the person empowered to bind the supplier;

  6. (f)

    technical parameters:

    • for boiler combination heaters, the technical parameters set out in Table 7, measured and calculated in accordance with Annex VII;

    • for heat pump combination heaters, the technical parameters set out in Table 8, measured and calculated in accordance with Annex VII;

    • for heat pump combination heaters where the information relating to a specific model comprising a combination of indoor and outdoor units has been obtained by calculation on the basis of design and/or extrapolation from other combinations, the details of such calculations and/or extrapolations, and of any tests undertaken to verify the accuracy of the calculations, including details of the mathematical model for calculating the performance of such combinations and details of the measurements taken to verify this model;

  7. (g)

    any specific precautions that shall be taken when the combination heater is assembled, installed or maintained.

Table 7

Technical parameters for boiler space heaters, boiler combination heaters and cogeneration space heaters

High-temperature regime means 60 °C return temperature at heater inlet and 80 °C feed temperature at heater outlet.

Low temperature means for condensing boilers 30 °C, for low-temperature boilers 37 °C and for other heaters 50 °C return temperature (at heater inlet).

Model(s): [information identifying the model(s) to which the information relates]
Condensing boiler: [yes/no]
Low-temperaturef1 boiler: [yes/no]
B11 boiler: [yes/no]
Cogeneration space heater: [yes/no]If yes, equipped with a supplementary heater: [yes/no]
Combination heater: [yes/no]
ItemSymbolValueUnitItemSymbolValueUnit
Rated heat outputPratedxkWSeasonal space heating energy efficiencyηs x%
For boiler space heaters and boiler combination heaters: Useful heat outputFor boiler space heaters and boiler combination heaters: Useful efficiency
At rated heat output and high-temperature regimef2 P4 x,xkWAt rated heat output and high-temperature regime η4 x,x%
At 30 % of rated heat output and low-temperature regime P1 x,xkWAt 30 % of rated heat output and low-temperature regime η1 x,x%
For cogeneration space heaters: Useful heat outputFor cogeneration space heaters: Useful efficiency
At rated heat output of cogeneration space heater with supplementary heater disabledPCHP100+Sup0 x,xkWAt rated heat output of cogeneration space heater with supplementary heater disabledηCHP100+Sup0 x,x%
At rated heat output of cogeneration space heater with supplementary heater enabledPCHP100+Sup100 x,xkWAt rated heat output of cogeneration space heater with supplementary heater enabledηCHP100+Sup100 x,x%
For cogeneration space heaters: Electrical efficiencySupplementary heater
At rated heat output of cogeneration space heater with supplementary heater disabledηel,CHP100+Sup0 x,x%Rated heat outputPsupx,xkW
At rated heat output of cogeneration space heater with supplementary heater enabledηel,CHP100+Sup100 x,x%Type of energy input
Auxiliary electricity consumptionOther items
At full loadelmaxx,xkWStandby heat lossPstby x,xkW
At part loadelminx,xkWIgnition burner power consumptionPign x,xkW
In standby modePSB x,xxxkWAnnual energy consumptionQHE xkWh or GJ
Sound power level, indoorsLWA xdB
For combination heaters:
Declared load profileWater heating energy efficiencyηwh x%
Daily electricity consumptionQelec x,xxxkWhDaily fuel consumptionQfuel x,xxxkWh
Annual electricity consumptionAECxkWhAnnual fuel consumptionAFCxGJ
Contact detailsName and address of the supplier.

Table 8

Technical parameters for heat pump space heaters and heat pump combination heaters

For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj).

If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.

Model(s): [information identifying the model(s) to which the information relates]
Air-to-water heat pump: [yes/no]
Water-to-water heat pump: [yes/no]
Brine-to-water heat pump: [yes/no]
Low-temperature heat pump: [yes/no]
Equipped with a supplementary heater: [yes/no]
Heat pump combination heater: [yes/no]
Parameters shall be declared for medium-temperature application, except for low-temperature heat pumps. For low-temperature heat pumps, parameters shall be declared for low-temperature application.
Parameters shall be declared for average, colder and warmer climate conditions.
ItemSymbolValueUnitItemSymbolValueUnit
Rated heat outputf3PratedxkWSeasonal space heating energy efficiencyηs x%
Declared capacity for heating for part load at indoor temperature 20 °C and outdoor temperature Tj Declared coefficient of performance or primary energy ratio for part load at indoor temperature 20 °C and outdoor temperature Tj
Tj = – 7 °CPdhx,xkW Tj = – 7 °CCOPd or PERdx,xx or x,x– or %
Tj = + 2 °CPdhx,xkW Tj = + 2 °CCOPd or PERdx,xx or x,x– or %
Tj = + 7 °CPdhx,xkW Tj = + 7 °CCOPd or PERdx,xx or x,x– or %
Tj = + 12 °CPdhx,xkW Tj = + 12 °CCOPd or PERdx,xx or x,x– or %
Tj = bivalent temperaturePdhx,xkW Tj = bivalent temperatureCOPd or PERdx,xx or x,x– or %
Tj = operation limit temperaturePdhx,xkW Tj = operation limit temperatureCOPd or PERdx,xx or x,x– or %
For air-to-water heat pumps: Tj = – 15 °C (if TOL < – 20 °C)Pdhx,xkWFor air-to-water heat pumps: Tj = – 15 °C (if TOL < – 20 °C)COPd or PERdx,xx or x,x– or %
Bivalent temperatureTbiv x°CFor air-to-water heat pumps: Operation limit temperatureTOLx°C
Cycling interval capacity for heatingPcychx,xkWCycling interval efficiencyCOPcyc or PERcycx,xx or x,x– or %
Degradation co-efficientf4 Cdhx,x—Heating water operating limit temperatureWTOLx°C
Power consumption in modes other than active modeSupplementary heater
Off modePOFF x,xxxkWRated heat output Psupx,xkW
Thermostat-off modePTO x,xxxkW
Standby modePSB x,xxxkWType of energy input
Crankcase heater modePCK x,xxxkW
Other items
Capacity controlfixed/variableFor air-to-water heat pumps: Rated air flow rate, outdoors—xm3/h
Sound power level, indoors/outdoorsLWA x / xdBFor water- or brine-to-water heat pumps: Rated brine or water flow rate, outdoor heat exchanger—xm3/h
Annual energy consumptionQHE xkWh or GJ
For heat pump combination heater:
Declared load profilexWater heating energy efficiencyηwh x%
Daily electricity consumptionQelec x,xxxkWhDaily fuel consumptionQfuel x,xxxkWh
Annual electricity consumptionAECxkWhAnnual fuel consumptionAFCxGJ
Contact detailsName and address of the supplier.

Annotations

Textual amendments

F1

Word in Annex 5 s. 2(c) substituted (31.12.2020) by The Ecodesign for Energy-Related Products and Energy Information (Amendment) (EU Exit) Regulations 2019 (S.I. 2019/539), reg. 1(3), Sch. 5 para. 9(8); 2020 c. 1, Sch. 5 para. 1(1)

Footnotes

f1

Low temperature means for condensing boilers 30 °C, for low-temperature boilers 37 °C and for other heaters 50 °C return temperature (at heater inlet).

f2

High-temperature regime means 60 °C return temperature at heater inlet and 80 °C feed temperature at heater outlet.

f3

For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj).

f4

If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.