Division 2 COMBINATION HEATERS
United Kingdom
For combination heaters, the technical documentation referred to in Article 3(2)(c) shall include:
- (a)
the name and address of the supplier;
- (b)
a description of the combination heater model sufficient for its unambiguous identification;
- (c)
where appropriate, the references of the F1designated standards applied;
- (d)
where appropriate, the other technical standards and specifications used;
- (e)
the identification and signature of the person empowered to bind the supplier;
- (f)
technical parameters:
for boiler combination heaters, the technical parameters set out in Table 7, measured and calculated in accordance with Annex VII;
for heat pump combination heaters, the technical parameters set out in Table 8, measured and calculated in accordance with Annex VII;
for heat pump combination heaters where the information relating to a specific model comprising a combination of indoor and outdoor units has been obtained by calculation on the basis of design and/or extrapolation from other combinations, the details of such calculations and/or extrapolations, and of any tests undertaken to verify the accuracy of the calculations, including details of the mathematical model for calculating the performance of such combinations and details of the measurements taken to verify this model;
- (g)
any specific precautions that shall be taken when the combination heater is assembled, installed or maintained.
Table 7
Technical parameters for boiler space heaters, boiler combination heaters and cogeneration space heaters
High-temperature regime means 60 °C return temperature at heater inlet and 80 °C feed temperature at heater outlet. | ||||||||
Low temperature means for condensing boilers 30 °C, for low-temperature boilers 37 °C and for other heaters 50 °C return temperature (at heater inlet). | ||||||||
| Model(s): [information identifying the model(s) to which the information relates] | ||||||||
| Condensing boiler: [yes/no] | ||||||||
| Low-temperaturef1 boiler: [yes/no] | ||||||||
| B11 boiler: [yes/no] | ||||||||
| Cogeneration space heater: [yes/no] | If yes, equipped with a supplementary heater: [yes/no] | |||||||
| Combination heater: [yes/no] | ||||||||
| Item | Symbol | Value | Unit | Item | Symbol | Value | Unit | |
|---|---|---|---|---|---|---|---|---|
| Rated heat output | Prated | x | kW | Seasonal space heating energy efficiency | ηs | x | % | |
| For boiler space heaters and boiler combination heaters: Useful heat output | For boiler space heaters and boiler combination heaters: Useful efficiency | |||||||
| At rated heat output and high-temperature regimef2 | P4 | x,x | kW | At rated heat output and high-temperature regime | η4 | x,x | % | |
| At 30 % of rated heat output and low-temperature regime | P1 | x,x | kW | At 30 % of rated heat output and low-temperature regime | η1 | x,x | % | |
| For cogeneration space heaters: Useful heat output | For cogeneration space heaters: Useful efficiency | |||||||
| At rated heat output of cogeneration space heater with supplementary heater disabled | PCHP100+Sup0 | x,x | kW | At rated heat output of cogeneration space heater with supplementary heater disabled | ηCHP100+Sup0 | x,x | % | |
| At rated heat output of cogeneration space heater with supplementary heater enabled | PCHP100+Sup100 | x,x | kW | At rated heat output of cogeneration space heater with supplementary heater enabled | ηCHP100+Sup100 | x,x | % | |
| For cogeneration space heaters: Electrical efficiency | Supplementary heater | |||||||
| At rated heat output of cogeneration space heater with supplementary heater disabled | ηel,CHP100+Sup0 | x,x | % | Rated heat output | Psup | x,x | kW | |
| At rated heat output of cogeneration space heater with supplementary heater enabled | ηel,CHP100+Sup100 | x,x | % | Type of energy input | ||||
| Auxiliary electricity consumption | Other items | |||||||
| At full load | elmax | x,x | kW | Standby heat loss | Pstby | x,x | kW | |
| At part load | elmin | x,x | kW | Ignition burner power consumption | Pign | x,x | kW | |
| In standby mode | PSB | x,xxx | kW | Annual energy consumption | QHE | x | kWh or GJ | |
| Sound power level, indoors | LWA | x | dB | |||||
| For combination heaters: | ||||||||
| Declared load profile | Water heating energy efficiency | ηwh | x | % | ||||
| Daily electricity consumption | Qelec | x,xxx | kWh | Daily fuel consumption | Qfuel | x,xxx | kWh | |
| Annual electricity consumption | AEC | x | kWh | Annual fuel consumption | AFC | x | GJ | |
| Contact details | Name and address of the supplier. | |||||||
Table 8
Technical parameters for heat pump space heaters and heat pump combination heaters
For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj). | ||||||||
If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9. | ||||||||
| Model(s): [information identifying the model(s) to which the information relates] | ||||||||
| Air-to-water heat pump: [yes/no] | ||||||||
| Water-to-water heat pump: [yes/no] | ||||||||
| Brine-to-water heat pump: [yes/no] | ||||||||
| Low-temperature heat pump: [yes/no] | ||||||||
| Equipped with a supplementary heater: [yes/no] | ||||||||
| Heat pump combination heater: [yes/no] | ||||||||
| Parameters shall be declared for medium-temperature application, except for low-temperature heat pumps. For low-temperature heat pumps, parameters shall be declared for low-temperature application. | ||||||||
| Parameters shall be declared for average, colder and warmer climate conditions. | ||||||||
| Item | Symbol | Value | Unit | Item | Symbol | Value | Unit | |
|---|---|---|---|---|---|---|---|---|
| Rated heat outputf3 | Prated | x | kW | Seasonal space heating energy efficiency | ηs | x | % | |
| Declared capacity for heating for part load at indoor temperature 20 °C and outdoor temperature Tj | Declared coefficient of performance or primary energy ratio for part load at indoor temperature 20 °C and outdoor temperature Tj | |||||||
| Tj = – 7 °C | Pdh | x,x | kW | Tj = – 7 °C | COPd or PERd | x,xx or x,x | – or % | |
| Tj = + 2 °C | Pdh | x,x | kW | Tj = + 2 °C | COPd or PERd | x,xx or x,x | – or % | |
| Tj = + 7 °C | Pdh | x,x | kW | Tj = + 7 °C | COPd or PERd | x,xx or x,x | – or % | |
| Tj = + 12 °C | Pdh | x,x | kW | Tj = + 12 °C | COPd or PERd | x,xx or x,x | – or % | |
| Tj = bivalent temperature | Pdh | x,x | kW | Tj = bivalent temperature | COPd or PERd | x,xx or x,x | – or % | |
| Tj = operation limit temperature | Pdh | x,x | kW | Tj = operation limit temperature | COPd or PERd | x,xx or x,x | – or % | |
| For air-to-water heat pumps: Tj = – 15 °C (if TOL < – 20 °C) | Pdh | x,x | kW | For air-to-water heat pumps: Tj = – 15 °C (if TOL < – 20 °C) | COPd or PERd | x,xx or x,x | – or % | |
| Bivalent temperature | Tbiv | x | °C | For air-to-water heat pumps: Operation limit temperature | TOL | x | °C | |
| Cycling interval capacity for heating | Pcych | x,x | kW | Cycling interval efficiency | COPcyc or PERcyc | x,xx or x,x | – or % | |
| Degradation co-efficientf4 | Cdh | x,x | — | Heating water operating limit temperature | WTOL | x | °C | |
| Power consumption in modes other than active mode | Supplementary heater | |||||||
| Off mode | POFF | x,xxx | kW | Rated heat output | Psup | x,x | kW | |
| Thermostat-off mode | PTO | x,xxx | kW | |||||
| Standby mode | PSB | x,xxx | kW | Type of energy input | ||||
| Crankcase heater mode | PCK | x,xxx | kW | |||||
| Other items | ||||||||
| Capacity control | fixed/variable | For air-to-water heat pumps: Rated air flow rate, outdoors | — | x | m3/h | |||
| Sound power level, indoors/outdoors | LWA | x / x | dB | For water- or brine-to-water heat pumps: Rated brine or water flow rate, outdoor heat exchanger | — | x | m3/h | |
| Annual energy consumption | QHE | x | kWh or GJ | |||||
| For heat pump combination heater: | ||||||||
| Declared load profile | x | Water heating energy efficiency | ηwh | x | % | |||
| Daily electricity consumption | Qelec | x,xxx | kWh | Daily fuel consumption | Qfuel | x,xxx | kWh | |
| Annual electricity consumption | AEC | x | kWh | Annual fuel consumption | AFC | x | GJ | |
| Contact details | Name and address of the supplier. | |||||||
Annotations
Textual amendments
- F1
Word in Annex 5 s. 2(c) substituted (31.12.2020) by The Ecodesign for Energy-Related Products and Energy Information (Amendment) (EU Exit) Regulations 2019 (S.I. 2019/539), reg. 1(3), Sch. 5 para. 9(8); 2020 c. 1, Sch. 5 para. 1(1)
Footnotes
- f1
Low temperature means for condensing boilers 30 °C, for low-temperature boilers 37 °C and for other heaters 50 °C return temperature (at heater inlet).
- f2
High-temperature regime means 60 °C return temperature at heater inlet and 80 °C feed temperature at heater outlet.
- f3
For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj).
- f4
If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.