Division 1.4 For the one-to-one replacement of existing medium power pole-mounted transformers with power ratings between 25 kVA and 400 kVA, the applicable maximum levels of load and no-load losses are not the ones in Tables I.1 and I.2, but those in Table I.6 below. Maximum allowable losses for kVA ratings other than those explicitly mentioned in Table I.6 shall be obtained by linear interpolation or extrapolation. The correction factors for special combinations of winding voltages indicated in Tables I.3a and I.3b are also applicable.F1
United Kingdom
For the one-to-one replacement of existing medium power pole-mounted transformers, the manufacturer, importer or authorised representative shall include in the technical documentation of the transformer the following information:
-
the address and contact details of the commissioner of the replacement transformer;
-
the station where the replacement transformer is to be installed. This shall be unequivocally identified either by a specific location or an specific installation type (e.g. technical description of the pole).
In the above cases, the manufacturer, importer or authorised representative shall notify the competent national market surveillance authorities.
With regard to the installation of new pole-mounted transformers, it is the requirements in Tables I.1 and I.2, in conjunction with Tables I.3a and I.3b where justified, which are applicable.
Table I.6: Maximum load and no-load losses (in W) for medium power liquid immersed pole-mounted transformers
| Maximum allowable losses for kVA ratings that fall in between the ratings given in Table I.6 shall be obtained by linear interpolation. | ||||
| Tier 1 (1 July 2015) | Tier 2 (1 July 2021) | |||
|---|---|---|---|---|
| Rated Power (kVA) | Maximum load losses (in W)f1 | Maximum no-load losses (in W) | Maximum load losses (in W) | Maximum no-load losses (in W) |
| 25 | Ck (900) | Ao (70) | Bk (725) | Ao (70) |
| 50 | Ck (1 100) | Ao (90) | Bk (875) | Ao (90) |
| 100 | Ck (1 750) | Ao (145) | Bk (1 475) | Ao (145) |
| 160 | Ck + 32 % (3 102) | Co (300) | Ck + 32 % (3 102) | Co – 10 % (270) |
| 200 | Ck (2 750) | Co (356) | Bk (2 333) | Bo (310) |
| 250 | Ck (3 250) | Co (425) | Bk (2 750) | Bo (360) |
| 315 | Ck (3 900) | Co (520) | Bk (3 250) | Bo (440) |
Annotations
Textual amendments
Footnotes
- f1
-
Maximum allowable losses for kVA ratings that fall in between the ratings given in Table I.6 shall be obtained by linear interpolation.
Notes on Division 1
Textual amendments
Footnotes
- f1
-
The European Commission Better Regulation Toolbox suggest using a value of 4 % for the social discount rate
https://ec.europa.eu/info/sites/info/files/file_import/better-regulation-toolbox-61_en_0.pdf